| 2008-06-04 14:04:07 | RESIDENTIAL (R3)DOORS AND WINDOWS REPLACEMENT, |
| | BUILDING REVIEW SECOND CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- PROVIDE 2 COMPLETE COPIES OF PRODUCT APPROVALS AS |
| | REQUIRED BY DCA RULE 9B-72 FOR: |
| | A) WINDOWS AS SHOWN ON FLOOR PLAN.(REPEAT |
| | COMMENT). |
| | FLOOR PLANSHOWS 5 DOUBLE HUNG WINDOWS.PRODUCT |
| | APPROVAL SUBMITTED NOA 03-0701.02 IS FOR |
| | SIDELITE/TRANSOM WINDOW ONLY.PROVIDE 2 COPIES OF |
| | CORRECT PRODUCT APPROVAL. |
| | B) FRENCH DOORS AS SHOWN ON FLOOR PLAN.NEED 2 |
| | COPIES. ONLY ONE WAS SUBMITTED. |
| | |
| | ***NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVALS FOR |
| | MULLIONS IF FLOOR PLAN DOESN'T SHOW ANY WINDOWS OR |
| | DOORS MULLED TOGETHER. |
| | |
| | 2- A) ENGINEER TO PROVIDE CALCULATIONS FOR DESIGN |
| | PRESSURES FOR WINDOW 101.ACCORDING TO SITE PLAN |
| | DRAWING. THIS WINDOW IS LOCATED ON THE END ZONE.SEE |
| | TABLE R301.2(2) AND FIGURE R301.2(8) OF 2004 FLORIDA |
| | RESIDENTIAL CODE AND REVISE AS REQUIRED. (REPEAT |
| | COMMENT). |
| | |
| | B) REVISE WOOD FRAME HEADER/SILL DETAIL:NOTE |
| | RELATING TO TOP HEADER BUCK SPECIFIES 1" X 3" P.T. WOOD |
| | BUCK CONT. WITH 1/4" X 2-1/4"WOOD SCREWS SPACED MAX. |
| | 24" O.C..WOOD SCREWS CAN'T BE USED TO ATTACH TO |
| | CONCRETE BLOCK. REVISE AS REQUIRED. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. (REPEAT COMMENT). |
| | |
| | 3-OWES $80.36 FOR UPDATED VALUATION AS REQUIRED BY |
| | SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | NOTE: ADDITIONAL RESUBMITTAL FEES WILL BE ASSESSED |
| | ALSO. |
| | |
| | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BYSEC. 713.13 FLORIDA STATUTE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |