| 2008-05-20 13:35:51 | RESIDENTIAL (R3)DOORS AND WINDOWS REPLACEMENT, |
| | BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- PROVIDE 2 COMPLETE COPIES OF PRODUCT APPROVALS AS |
| | REQUIRED BY DCA RULE 9B-72 FOR: |
| | A) WINDOWS AS SHOWN ON PLANS. |
| | B) FRENCH DOORS AS SHOWN ON PLANS. |
| | C) SHUTTERS (SEE ITEM #4). |
| | |
| | ***INFORMATION SUBMITTED IS NOT A PRODUCT APPROVAL. |
| | |
| | 2- A) ENGINEER TO PROVIDE CALCULATIONS FOR DESIGN |
| | PRESSURES FOR WINDOW 101.ACCORDING TO SITE PLAN |
| | DRAWING. THIS WINDOW IS LOCATED ON THE END ZONE.SEE |
| | TABLE R301.2(2) AND FIGURE R301.2(8) OF 2004 FLORIDA |
| | RESIDENTIAL CODE AND REVISE AS REQUIRED. |
| | |
| | B) REVISE WOOD FRAME HEADER/SILL DETAIL:NOTE |
| | RELATING TO TOP HEADER BUCK SPECIFIES 1" X 3" P.T. WOOD |
| | BUCK CONT. WITH 1/4" X 2-1/4"WOOD SCREWS SPACED MAX. |
| | 24" O.C..WOOD SCREWS CAN'T BE USED TO ATTACH TO |
| | CONCRETE BLOCK. REVISE AS REQUIRED. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW IF INCLUDING WINDOWSAND DOORS REMOVAL, |
| | INSTALLATION OF 5 DOUBLE HUNG "ANDERSEN" WINDOW AND ONE |
| | PAIR OFFRENCH DOORS AND ENGINEERING SUBMITTED.NEED |
| | TO UPDATE VALUATION TO INCLUDE ALL THESE ITEMS. SEC. |
| | 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- IF DOORS AND WINDOWS DON'T HAVE IMPACT GLASS, THEN |
| | NEED TO PROVIDEPRODUCT APPROVAL FOR STORM SHUTTERS AS |
| | REQUIRED BY SEC. R301.2.1.2 OF 2004 FLORIDA RESIDENTIAL |
| | CODE.ALSO,PROVIDECOMPLETE INSTALLATION SCHEDULE. |
| | SEE ATTACHED SAMPLE OF INSTALLATION SCHEDULE.ALSO, |
| | CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING |
| | CONDITIONS (EG: WALL MOUNTED, BUILT OUT, ETC)AND |
| | SPECIFIC ANCHOR TYPE AND SPACING TO BE USED.SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY |
| | COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 5- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BYSEC. 713.13 FLORIDA STATUTE. |
| | |