| Plan Review Notes For Permit 08050491 |
| Permit Number |
08050491 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-02 16:45:10 | 2004 FBC W/2007 REVISIONS | | | INSTALL TRAILER TIE DOWNS | | | | | | DENIED BY BUILDING | | | | | | 1) THERE IS NO RECORD WITH THE CITY OF A PERMIT BEING | | | ISSUED TO INSTALL A PERMANENT TRAILER AT THIS LOCATION. | | | PLEASE APPLY FOR A PERMIT TO INSTALL THE TRAILER. | | | | | | 2) SUBMIT 2 COPIES OF A SURVEY/SITE PLAN SPECIFYING THE | | | DISTANCES TO PROPERTY LINES AND OTHER STRUCTURES ON THE | | | SAME PROPERTY. FBC TABLE 602 | | | | | | 3) SPECIFY THE TYPE OF CONSTRUCTION. FBC 602. | | | | | | 4) SPECIFY THE OCCUPANCY TYPE FOR THE TRAILER. FBC | | | 302.1 | | | | | | 5) PROVIDE THE WINDSPEED DESIGN DATA. FBC 1609 | | | | | | 6) SUBMIT TWO COPIES OF APPROVED MANUFACTURED BUILDING | | | PLANS OR MOBILE HOME DESIGN INFORMATION. DCA RULE 9B-1, | | | FBC 428 AND MOBILE/MANUFACTURED HOME STANDARDS 15C-1. | | | | | | 7) SHOW COMPLIANCE WITH ACCESSIBILITY, IF REQUIRED. FBC | | | 11-4. | | | | | | 8) PROVIDE ANCHOR DETAILS. FBC 106.1.1* CITY | | | AMENDMENTS. | | | | | | 9) SUBMIT PRODUCT APPROVALS FOR IMPACT PROTECTION | | | DEVICES FOR GLAZED OPENINGS. FBC 1609.1.4 AND DCA RULE | | | 9B-72. | | | | | | 10) COUNTY IMPACT FEES MAY BE REQUIRED. | | | | | | 11) ADDITIONAL PERMITS MAY BE REQUIRED FOR ELECTRIC, | | | MECHANICAL, ETC. | | | | | | 12) ADDITIONAL COMMENTS MAY RESULT WHEN THE ABOVE ITEMS | | | ARE ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|