| 2008-06-17 16:47:25 | ***PROVISO*** |
| | PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT PERMANENTLY |
| | INSTALLED EQUIPMENT POWERED BY INTERNALCOMBUSTION |
| | ENGINES SHALL BE INSTALLED IN ACCORDANCE WITH |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA 37. |
| | NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION |
| | ENGINES & GAS TURBINES: 4.1.4ENGINES (GENERATORS) |
| | LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS |
| | IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING |
| | COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT REQUIRED |
| | WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE |
| | RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF |
| | ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, |
| | AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE |
| | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| | MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 |
| | EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES |
| | OR |
| | WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION |
| | INTAKES. |
| | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS |
| | LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE |
| | TERMINATION POINT |
| | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF |
| | STRUCTURE. |
| | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL |
| | EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, |
| | GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED |
| | CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E. |
| | FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS. |
| | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES |
| | AROUND EQUIPMENT FOR SERVICING,AND PROVIDE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE |
| | FOR THE FIELD INSPECTOR. |