| 2008-05-27 09:00:33 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET D-1 PLEASE ADD THE FOLLOWING TO GENERAL |
| | DEMOLITION NOTES: |
| | PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE |
| | INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE |
| | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A PLUMBING |
| | PERMIT IS REQUIRED AND AN INSPECTION IS REQUIRED OF |
| | PLUMBING DEMO WORK PRIOR TO COVERING DEMO WORK WITH |
| | FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS. |
| | |
| | 2. SHEET MEP-1 SANITARY RISER DIAGRAM: PLEASE CORRECT |
| | THE FOLLOWING ITEMS PER FBC-2004 PLUMBING. |
| | |
| | A} THE WASHING MACHNE AND LAUNDRY TRAY MUST DRAIN |
| | DOWNSTREAM OF WET VENTED BATHROOM #4. PER SECTION 909.1 |
| | WET VENT PERMITTED. |
| | |
| | B} A THREE INCH CLEANOUT IS REQUIRED FOR THE WASHING |
| | MACHINE STACK AND IT SHALL BE LOCATED AT FOUR FEET |
| | ABOVE FINNISH FLOOR. PER SECTION 708.7 MINIMUM SIZE AND |
| | SECTION 708.9 ACCESS. |
| | |
| | C} THE BIDET IN THE MASTER BATH REQUIRES A WATER SEAL |
| | TRAP. PER SECTION 1002.1 TRAP REQUIRED. |
| | |
| | D} CLEARLY INDICATE THAT THE CLEANOUTS AT THE JUNCTION |
| | OF THE BUILDING DRAIN AND BUILDING SEWER WILL BE |
| | TWO-WAY CLEANOUTS. PER SECTION 708.3.5. |
| | |
| | E} CLEARLY SIZE ALL TRAPS OR PROVIDE A FIXTURE TRAP |
| | SIZING SCHEDULE. PER SECTION 701.1 SCOPE AND (W.P.B. AS |
| | AMENDED) SECTION 106.3.5.4 RESIDENTIAL (9) PLUMBING. |
| | |
| | F} THE ICE MAKER BY THE BAR SINK MAY REQUIRE A DRAIN. |
| | PLEASE SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR |
| | THE ICE MAKER AND DESIGN ACCORDINGLY IF APPLICABLE. PER |
| | SECTION 701.1 SCOPE. |
| | |
| | 3. SHEET MEP-1 PLUMBING NOTES #11: INDICATES APPROVED |
| | AIR CHAMBER. AIR CHAMBERS ARE NOT APPROVED UNLESS |
| | INSTALLED PER STANDARD PDI-WH-201 A RECHARGEABLE TYPE |
| | OF AIR CHAMBER. (DETAIL REQUIRED OR DELETE AIR CHAMBERS |
| | ON THE RESUBMITTAL) |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |