Plan Review Notes
Plan Review Notes For Permit 08050488
Permit Number 08050488
Review Stop P
Sequence Number 1
Notes
Date Text
2008-05-27 09:00:33PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET D-1 PLEASE ADD THE FOLLOWING TO GENERAL
 DEMOLITION NOTES:
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A PLUMBING
 PERMIT IS REQUIRED AND AN INSPECTION IS REQUIRED OF
 PLUMBING DEMO WORK PRIOR TO COVERING DEMO WORK WITH
 FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS.
  
 2. SHEET MEP-1 SANITARY RISER DIAGRAM: PLEASE CORRECT
 THE FOLLOWING ITEMS PER FBC-2004 PLUMBING.
  
 A} THE WASHING MACHNE AND LAUNDRY TRAY MUST DRAIN
 DOWNSTREAM OF WET VENTED BATHROOM #4. PER SECTION 909.1
 WET VENT PERMITTED.
  
 B} A THREE INCH CLEANOUT IS REQUIRED FOR THE WASHING
 MACHINE STACK AND IT SHALL BE LOCATED AT FOUR FEET
 ABOVE FINNISH FLOOR. PER SECTION 708.7 MINIMUM SIZE AND
 SECTION 708.9 ACCESS.
  
 C} THE BIDET IN THE MASTER BATH REQUIRES A WATER SEAL
 TRAP. PER SECTION 1002.1 TRAP REQUIRED.
  
 D} CLEARLY INDICATE THAT THE CLEANOUTS AT THE JUNCTION
 OF THE BUILDING DRAIN AND BUILDING SEWER WILL BE
 TWO-WAY CLEANOUTS. PER SECTION 708.3.5.
  
 E} CLEARLY SIZE ALL TRAPS OR PROVIDE A FIXTURE TRAP
 SIZING SCHEDULE. PER SECTION 701.1 SCOPE AND (W.P.B. AS
 AMENDED) SECTION 106.3.5.4 RESIDENTIAL (9) PLUMBING.
  
 F} THE ICE MAKER BY THE BAR SINK MAY REQUIRE A DRAIN.
 PLEASE SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR
 THE ICE MAKER AND DESIGN ACCORDINGLY IF APPLICABLE. PER
 SECTION 701.1 SCOPE.
  
 3. SHEET MEP-1 PLUMBING NOTES #11: INDICATES APPROVED
 AIR CHAMBER. AIR CHAMBERS ARE NOT APPROVED UNLESS
 INSTALLED PER STANDARD PDI-WH-201 A RECHARGEABLE TYPE
 OF AIR CHAMBER. (DETAIL REQUIRED OR DELETE AIR CHAMBERS
 ON THE RESUBMITTAL)
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  