Plan Review Notes
Plan Review Notes For Permit 08050488
Permit Number 08050488
Review Stop M
Sequence Number 1
Notes
Date Text
2008-05-22 08:11:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 2) ENERGY CALCULATIONS ARE MISSING THE JOB ADDRESS,
 JURISDICTION NUMBER, ETC. PLEASE CORRECT.
  
 3) COOLING LOAD CALCULATIONS MAY NOT BE DONE BY A WORSE
 CASE SCENARIO, BUT MUST BE DONE TO THE SPECIFIC
 BUILDINGS ORIENTATION, PER FLORIDA BUILDING COMMISSION
 DECLARATORY STATEMENT DCA06-DEC-130. PLEASE CORRECT.
  
 4) THE GAS CLOTHES DRYERS ARE IN A CONFINED SPACE
 PLEASE PROVIDE FOR COMBUSTION AIR AND MAKE UP AIR, PER
 2004 FBC/R G2407.1, G2407.4, AND G2407.5.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]