Plan Review Notes
Plan Review Notes For Permit 08050488
Permit Number 08050488
Review Stop G
Sequence Number 1
Notes
Date Text
2008-05-27 11:17:49GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET MEP-1 GAS LINE ISOMETRIC PLEASE CORRECT THE
 FOLLOWING PER FBC-2004 FUEL GAS:
  
 A} THE SUBMITTED GAS ISOMETRIC IS NOT INDICATING
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. A
 GAS PLAN REVIEW CAN NOT BE DONE UNTIL AN ACCURATE
 LONGEST LENGTH OF THE GAS SYSTEM HAS BEEN ESTABLISED.
 PLEASE REFERENCE THE RED CIRCLED YELLOW HIGH LIGHTED
 CUT SECTIONS WITH NO CORRESPONDING LENGTHS INDICATED.
 PER SECTION 401.1 SCOPE.
  
 B} PLEASE CORRELATE BTU LOAD CALCULATIONS FOR THE
 WATER HEATER. THE GAS ISOMTRIC IS INDICATING A BUT LOAD
 OF 100,000 HOWEVER THE GAS LOAD CALCULATIONS ARE
 INDICATING THE BTU LOAD FOR THE WATER HEATER AS
 250,000. PER SECTION 401.1 SCOPE.
  
 C} CLEARLY INDICATE THE GENERATOR AS BEING "FUTURE"
 AND THAT THE GAS PIPING TO THE GENERATOR SHALL BE
 CAPPED GAS TIGHT. SECTION 401.1 SCOPE AND SECTION
 404.12 OUTLET CLOSURERS. NOTE: PIPING TO A FUTURE
 GENERATOR SHALL BE AT OWN RISK UNTIL A RESIDENTIAL
 GENERATOR APPLICATION HAS BEEN APPLIED FOR AND THE
 GENERATORS LOCATION HAS BEEN APPROVED BY ZONING.
  
 D} SHEET MEP-1 "GAS NOTES"#7 STATES THAT THE
 INTERIOR MAY BE PIPED WITH CORRUGATED STAINLESS STEEL
 TUBING. PLEASE KNOW THAT YOU ARE CIRCUMVENTING YOUR
 NOTE #5 BY PUTTING THIS IN THE GAS NOTES DUE TO THE
 DIFFERENCE IN PIPING MATERIAL BTU LOAD CAPACITIES. CSST
 HAS LESS BTU LOAD CAPACITY AS SCH. 40 METALLIC PIPE. IF
 IT IS THE INTENT TO USE CSST THEN THE GAS ISOMETRIC
 SHALL CLEARLY INDICATE WHICH CUT SECTIONS ARE TO BE
 CSST AND SIZED ACCORDINGLY PER TABLE 402.4(14) OR
 DELETE NOTE #7 FROM RESUBMITTED PLANS.
 NOTE: THE CALCULATED LONGEST LENGTH WITH THE INDICATED
 CORRESPONING LENGTHS IS 97' (REFERENCE COMMENT A). THE
 GAS PLAN REVIEW WAS DONE WITH THE LONGEST LENGTH AS
 100'. PLEASE REFERENCE THE RED LINE CORRECTIONS TO THE
 GAS ISOMETRIC USING FBC-2004 FUEL GAS TABLES 402.4 (2)
 AND 402.4(20). PLEASE REFERENCE THESE GAS TABLES AS
 WELL AS THE CSST TABLE 402.4(14) ATTACHED TO THESE
 COMMENTS FOR REFERENCE FOR THE RESUBMITTAL.
  
 2. SHEET A-1 FLOOR PLAN INDICATES AN 80 GAL. GAS WATER
 HEATER IN THE GARAGE HOWEVER THERE IS NO PROTECTION
 BEING INDICATED FOR THE WATER HEATER. PLEASE INDICATE
 THE REQUIRED PROTECTION FOR THE WATER HEATER. PER
 FBC-2004 FUEL GAS SECTION 303.4 PROTECTION FROM
 PHYSICAL DAMAGE.
  
 3. SHEET A-1 PLEASE CLEARLY INDICATE THE GAS METER
 LOCATION. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 4. PLEASE REFERENCE MECHANICAL COMMENTS #1 AND #4 AND
 COMPLY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]