| 2008-05-27 11:17:49 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET MEP-1 GAS LINE ISOMETRIC PLEASE CORRECT THE |
| | FOLLOWING PER FBC-2004 FUEL GAS: |
| | |
| | A} THE SUBMITTED GAS ISOMETRIC IS NOT INDICATING |
| | CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. A |
| | GAS PLAN REVIEW CAN NOT BE DONE UNTIL AN ACCURATE |
| | LONGEST LENGTH OF THE GAS SYSTEM HAS BEEN ESTABLISED. |
| | PLEASE REFERENCE THE RED CIRCLED YELLOW HIGH LIGHTED |
| | CUT SECTIONS WITH NO CORRESPONDING LENGTHS INDICATED. |
| | PER SECTION 401.1 SCOPE. |
| | |
| | B} PLEASE CORRELATE BTU LOAD CALCULATIONS FOR THE |
| | WATER HEATER. THE GAS ISOMTRIC IS INDICATING A BUT LOAD |
| | OF 100,000 HOWEVER THE GAS LOAD CALCULATIONS ARE |
| | INDICATING THE BTU LOAD FOR THE WATER HEATER AS |
| | 250,000. PER SECTION 401.1 SCOPE. |
| | |
| | C} CLEARLY INDICATE THE GENERATOR AS BEING "FUTURE" |
| | AND THAT THE GAS PIPING TO THE GENERATOR SHALL BE |
| | CAPPED GAS TIGHT. SECTION 401.1 SCOPE AND SECTION |
| | 404.12 OUTLET CLOSURERS. NOTE: PIPING TO A FUTURE |
| | GENERATOR SHALL BE AT OWN RISK UNTIL A RESIDENTIAL |
| | GENERATOR APPLICATION HAS BEEN APPLIED FOR AND THE |
| | GENERATORS LOCATION HAS BEEN APPROVED BY ZONING. |
| | |
| | D} SHEET MEP-1 "GAS NOTES"#7 STATES THAT THE |
| | INTERIOR MAY BE PIPED WITH CORRUGATED STAINLESS STEEL |
| | TUBING. PLEASE KNOW THAT YOU ARE CIRCUMVENTING YOUR |
| | NOTE #5 BY PUTTING THIS IN THE GAS NOTES DUE TO THE |
| | DIFFERENCE IN PIPING MATERIAL BTU LOAD CAPACITIES. CSST |
| | HAS LESS BTU LOAD CAPACITY AS SCH. 40 METALLIC PIPE. IF |
| | IT IS THE INTENT TO USE CSST THEN THE GAS ISOMETRIC |
| | SHALL CLEARLY INDICATE WHICH CUT SECTIONS ARE TO BE |
| | CSST AND SIZED ACCORDINGLY PER TABLE 402.4(14) OR |
| | DELETE NOTE #7 FROM RESUBMITTED PLANS. |
| | NOTE: THE CALCULATED LONGEST LENGTH WITH THE INDICATED |
| | CORRESPONING LENGTHS IS 97' (REFERENCE COMMENT A). THE |
| | GAS PLAN REVIEW WAS DONE WITH THE LONGEST LENGTH AS |
| | 100'. PLEASE REFERENCE THE RED LINE CORRECTIONS TO THE |
| | GAS ISOMETRIC USING FBC-2004 FUEL GAS TABLES 402.4 (2) |
| | AND 402.4(20). PLEASE REFERENCE THESE GAS TABLES AS |
| | WELL AS THE CSST TABLE 402.4(14) ATTACHED TO THESE |
| | COMMENTS FOR REFERENCE FOR THE RESUBMITTAL. |
| | |
| | 2. SHEET A-1 FLOOR PLAN INDICATES AN 80 GAL. GAS WATER |
| | HEATER IN THE GARAGE HOWEVER THERE IS NO PROTECTION |
| | BEING INDICATED FOR THE WATER HEATER. PLEASE INDICATE |
| | THE REQUIRED PROTECTION FOR THE WATER HEATER. PER |
| | FBC-2004 FUEL GAS SECTION 303.4 PROTECTION FROM |
| | PHYSICAL DAMAGE. |
| | |
| | 3. SHEET A-1 PLEASE CLEARLY INDICATE THE GAS METER |
| | LOCATION. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. |
| | |
| | 4. PLEASE REFERENCE MECHANICAL COMMENTS #1 AND #4 AND |
| | COMPLY. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |