Plan Review Notes
Plan Review Notes For Permit 08050488
Permit Number 08050488
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-20 16:53:53 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC CHAPTER 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET MEP-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1}THE EQUIPMENT GROUND BETWEEN THE METER AND PANEL
 "A" ON THE RISER DIAGRAM CREATES A PARALLEL PATH TO
 GROUND WITH THE NEUTRAL AND MUST BE REMOVED. 250.6.2005
 NEC.
  
 2} PANEL "A" MUST BE SERVICE RATED AND HAVE A MAIN
 BREAKER, OR A DISCONNECT IS REQUIRED OUTSIDE BETWEEN
 THE METER AND PANEL. 230.70
  
 3} THE RISER INDICATES 3# 6CU FEEDERS FOR PANEL "B",
 THE PANEL SCHEDULE INDICATES # 8.
  
 4} THE 30 AMP OCP FOR PANEL "B" IS NOT LARGE ENOUGH FOR
 THE 48 AMP LOAD CALCULATED FOR THAT PANEL. 310.16.
  
 5} #4 FEEDERS FROM THE METER TO THE 133 AMP LOAD ON
 PANEL "A" (RATED AT 200 AMPS) IS IN VIOLATION OF
 310.15(B)(6). MINIMUM OF 2/0 CU CONDUCTORS.
  
 6} THE AHU OCP, CIRCUIT 28,30 PANEL "A" IS NOT LARGE
 ENOUGH FOR THE 8500 WATT LOAD @ 125%. SEE 424.3(B),
 310.16, 240.6.(44 AMPS).
  
 7} CIRCUITS 36,38 FOR AHU #2, THE OCP IS TOO LARGE, SEE
 REFERENCES, COMMENT #6. (28 AMPS@ 125%).
  
 8} THE WASHER CIRCUIT #23 PANEL "A" (LAUNDRY) MUST BE
 CALCULATED AT 1500 WATTS PER 210.11(C)(2).
  
 NOTE: THE 3/0 GROUNDING ELECTRODE CONDUCTOR ON THE
 RISER IS NOT A VIOLATION OF 250.66, BUT A #2 IS ALL
 THAT'S REQUIRED. WHAT IS SHOWN ON THE PERMIT SET OF
 PLANS MUST BE INSTALLED OR A REVISION SUBMITTED TO
 CHANGE THAT SIZE AT A LATTER DATE.
  
 COMMENTS FROM SHEET E-1.
  
 9} R313.1 SMOKE ALARMS.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 TWO ALARMS NEED TO BE ADDED IN THE HALL OUTSIDE OF
 BEDROOM #4 AND THE GUEST BEDROOM TO MEET THE INTENT OF
 R 313.1.2 . ALSO SEE THE DEFINITION OF "SMOKE
 DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS
 OR ALARMS, TO AVOID CONFUSION IN THE FIELD. IF USING
 DETECTORS INDICATE THE LOCATIONS OF THE SOUNDING
 DEVICES.
  
 10} AT LEAST ONE GFI RECEPTACLE MUST BE INSTALLED IN
 THE GARAGE FOR COMPLIANCE WITH 210.52(G).
  
 11} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. SEVERAL ARE
 MISSING ALONG THE COUNTER.
  
 12} A RECEPTACLE MUST BE ADDED TO THE BATH ADJACENT TO
 THE FOYER TO COMPLY WITH 210.52(D), MUST BE GFI PER
 210.8(A)(1).
  
 13} THE WHIRLPOOL PUMP RECEPTACLE MUST BE GFI PROTECTED
 PER 680.43(A)(3).
  
 14} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER