| Date |
Text |
| 2008-05-19 10:56:57 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. |
| | THE VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE |
| | TOTAL COST OF LABOR AND MATERIALS. VALUATION REFERENCES |
| | MAY INCLUDE THE LATEST PUBLISHED DATA OF A NATIONAL |
| | CONSTRUCTION COST ANALYSIS (MARSHALL-SWIFT, MEANS, |
| | ECT...) ADJUST THE VALUE AT THE PERMIT CLERK'S DESK AND |
| | PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING OR |
| | PROVIDE A COPY OF THE SIGNED CONRACT BY BOTH PARTIES |
| | (CONTRACTOR AND CUSTOMER) TO VERIFY THE PERMIT |
| | APPLICATION VALUE. PER (W.P.B. AS AMENDED) SECTION |
| | 108.3 BUILDING PERMIT VALUATION. |
| | |
| | 2. THE PERMIT APPLICATION INDICATES "REMOVE BATHTUB |
| | INSTALL WALK-IN BATHTUB", HOWEVER THE SUBMITTED PLANS |
| | ARE NOT CLEARLY INDICATING THE BATHTUB TO BE REMOVED. |
| | PLANS ONLY INDICATE AN EXISTING BATHTUB AND THE |
| | PROPOSED WALK-IN BATHTUB. PLEASE PROVIDE AN EXISTING |
| | FLOOR PLAN OF UNIT #903 AND CLEARLY INDICATE WHERE THE |
| | PROPSED WORK IS TO DONE AND THE LOCATION OF THE BATHTUB |
| | TO BE REMOVED. PER (W.P.B. AS AMENDED) SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. PROVIDE DETAILS OF HOW THE DEMOED BATHTUB AND THE |
| | PROPOSED WALK-IN BATHTUB ARE TO BE FIRESTOPPED |
| | COMPLIANT WITH FBC-2004 BUILDING CHAPTER 7, |
| | FIRE-RESISTANCE-RATED CONSTRUCTION. |
| | |
| | 4. CLEARLY INDICATE WHICH MODEL TSANGKUO INDUSTRIAL |
| | CO.LTD, CHROME PLATED, DECK MOUNT, SINGLE HANDLE, |
| | TUB/SHOWER FAUCET WITH HAND SHOWER IS BEING USED ON THE |
| | RESUBMITTAL. THE SUBMITTAL IS INDICATING SIX (6) MODEL |
| | NUMBERS. PER (W.P.B. AS AMENDED) SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. THE RELIANCE WATER CONTROL, HEATGUARD TMV2 DOES NOT |
| | CONFORM TO ASSE 1016-96. PLEASE REMOVE THIS SUBMITTAL |
| | ON THE RESUBMITTAL OR PROVE COMPLIANCE. PER FBC-2004 |
| | PLUMBING SECTION 424.3 SHOWER VALVES. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |