| Date |
Text |
| 2008-09-08 14:48:09 | 2004 FBC W/2007 REVISIONS |
| | ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. |
| | |
| | 2) THE ADDITION TO THE EXISTING HOUSE IS REQUIRED TO BE |
| | INSULATED, HAVE ELECTRICAL WIRING, ETC. IN ORDER TO |
| | COMPLY WITH CODE AND WILL BE SUBSTANTIALLY COMPLETED, |
| | THEREFORE, A SHELL PERMIT CAN NOT BE ISSUED FOR THIS |
| | PROJECT. THE VALUE OF THE PROJECT HAS BEEN ADJUSTED TO |
| | ACCOUNT FOR THE REDUCTION IN SQUARE FOOTAGE TO 445 |
| | SQFT. THE VALUE HAS BEEN ADJUSTED TO $47,067.00. |
| | ADDITIONAL PERMIT FEES OF $ 639.00 ARE DUE. SEE FBC |
| | 108.3* CITY AMENDMENTS. FEES MUST BE PAID BEFORE PLANS |
| | ARE RELEASED. |
| | |
| | 3) SUBMIT 2 COPIES OF A SURVEY THAT AGREES WITH THE |
| | DIMENSIONS OF THE SITE PLAN ON SHEET S-1. |
| | |
| | 4) THE ENERGY CALCULATION FORM IS NOT FILLED OUT |
| | PROPERLY. IN ORDER TO USE FORM 600C-04R THE |
| | PRESCRIPTIVE METHOD THE MAXIMUM GLASS TO FLOOR AREA |
| | ALLOWED CAN NOT EXCEED 50 PERCENT. REVISE OPENINGS OR |
| | USE ANOTHER METHOD TO SHOW COMPLIANCE. THERE ARE NOT |
| | ANY WALLS OF THE ADDITION ADJACENT TO UNCONDITIONED |
| | SPACE SHOWN ON THE PLANS. THE CEILING INSULATION IS |
| | LISTED AS R3-0 ON THE FORM AND IT SHOULD BE R30. THE |
| | OWNER/AGENT IS REQUIRED TO SIGN THE FORM. PLEASE |
| | CORRECT. SEE FBC 13-600 METHOD C. |
| | |
| | 5) THE PRODUCT APPROVALS HAVE BEEN CHANGED TO LARGE |
| | MISSILE IMPACT WINDOWS AND DOORS. THE STORM PANEL |
| | INSTALLATION SCHEDULE IS NO LONGER REQUIRED. PLEASE |
| | REMOVE IT FROM SUBMITTALS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |