Plan Review Notes
Plan Review Notes For Permit 08050430
Permit Number 08050430
Review Stop P
Sequence Number 1
Notes
Date Text
2008-05-22 14:16:40PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS (CHAPTER 41, SWIMMING POOLS), CITY OF
 WEST PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.),
 FLORIDA ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA
 STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE PLAN DOES NOT REFLECT THE POOL SPECIFICATIONS.
 PER (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 A} THE LOCATION OF THE AUTO-FILL IS MISSING. CLEARLY
 INDICATE THE AUTO-FILL LOCATION AND ADD A NOTE THAT THE
 POTABLE WATER SUPPLY TIE-IN FOR THE AUTO-FILL SHALL BE
 BY A LICENSED PLUMBING CONTRACTOR. PER FS 489.105(3)(M)
 PLUMBING CONTRACTOR.
  
 B} CLEARLY INDICATE THE LOCATION OF THE OVERFLOW ON
 THE POOL PLAN.
  
 2. CLEARLY INDICATE THE LOCATION OF THE AQUALINK RS-6
 SYSTEM AND AQUA PURE SALT SYSTEM ON THE EQUIPMENT
 LAYOUT. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 NOTE: THE SUBMITTED MANUFACTURER'S SPECIFICATION SHEET
 FOR THE GAS POOL HEATER DOES NOT INDICATE A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY (THE
 FOLLOWING ARE EXAMPLES CSA, AGA, UL). PLEASE SUBMIT A
 SPEC. SHEET WITH A LISTING.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  