| Plan Review Notes For Permit 08050423 |
| Permit Number |
08050423 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-16 10:50:47 | 2004 FBC W/2007 REVISIONS | | | REMOVE AND REINSTALL CHILLER ON NEW STAND | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY THE EXISTING ATTACHMENT OF THE CHILLER UNIT | | | TO THE 6 X 6 STEEL FRAME. FBC 1609.1.3 REQUIRES THE | | | UNIT TO BE ANCHORED TO RESIST OVERTURNING, UPLIFT AND | | | SLIDING. | | | | | | 2) IF THE POINT LOADING OF THE NEW STAND WILL BE | | | GREATER THAN THE GRAVITY LOADS IMPOSED BY THE ORIGINAL | | | INSTALLATION, SUBMIT AN ANALYSIS FROM AN ENGINEER | | | SHOWING THAT THE ROOF CAN SUPPORT THE NEW CONCENTRATED | | | LOADS. | | | | | | 3) A GENERAL CONTRACTOR WILL BE REQUIRED TO PULL THE | | | PERMIT TO INSTALL THE STAND FOR THE CHILLER. FS 489. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|