| 2008-05-21 09:53:33 | ****************PROVISO*************** | | | NOTE: THE FLOOR DRAIN WILL REQUIRE A TRAP PRIMER. PER | | | FBC-2004 PLUMBING SECTION 1002.4 TRAP SEALS. EACH | | | FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS THAN | | | 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 MM), | | | OR DEEPER FOR SPECIAL DESIGNS RELATING TO ACCESSIBLE | | | FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO LOSS BY | | | EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE | | | INSTALLED. A TRAP SEAL PRIMER VALVE SHALL CONFORM TO | | | ASSE 1018 OR ASSE 1044. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|