2008-06-03 18:50:27** DENIED**
  
  
 1) NOTE:PLEASE SEE THE LIGHTING WHICH IS BEING SHOWN
 ON ELECTRICAL LIGHTING PLANS NOTED WITH NOTE #4 SHALL
 NOT HAVE PROVISIONS FOR FUTURE LIGHTS. BASED ON THE
 METHOD OF CALCULATIONS SUBMITTED ALONG WITH THE MAXIMUM
 ALLOWED WATTAGE AS SHOWN THESE LIGHT FIXTURES WOULD
 PLACED THE ALLOWANCE WAY OVER THE TABLE ALLOWANCE AND
 PERMITTED WATTAGE CONSUMPTION PER 13-415.2.ABC.1.1,
 .1.2, 13-415.2.C.
 PLEASE ADJUST PLANS AND PLEASE REMOVED FIXTURES. THE
 DESIGN OF FIXTURES, NUMBER OF FIXTURES, WATTAGE OF
 FIXTURES ETC MAY BE REVISED, HOWEVER MAT NOT BE DONE AS
 SHOWN.
 PLEASE ALSO KNOW THE *ALTERNATE LIGHTING* SHOWN ON E0.1
 IS NOT PART OF THE DESIGN AT THIS TIME. IF THIS IS
 GOING TO BE USED THEN PLANS NEED TO BE REVISED
 ACCORDINGLY.
  
 2) NOTE: PLEASE VERIFY ACTUAL ROOM DESIGNATION FOR
 IT/PHONE ROOM #123. IF THIS IS ACTUALLY AN IT ROOM THEN
 PLEASE SHOW COMPLIANCE WITH 645 OF THE NEC. IF THIS NOT
 AN IT ROOM PLEASE REMOVE THE IT DESIGNATION.
  
 3) NOTE: PLEASE BE SURE ALL CIRCUITING ON PLANS
 COORDINATES WITH THE SUBMITTED PANEL SCHEDULES.
 PLEASE SUBMIT OTHER PANEL SCHEDULES FOR ITEMS LISTED ON
 PLANS, BUT NO SCHEDULE SUBMITTED.
 FOR EXAMPLE:
 PLEASE SEE ROOM 125, CIRCUIT SHOWN TO PANEL HA-7 YET NO
 HA PANEL WAS SUBMITTED.
  
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 4) NOTE: REDLINED MDP AS DONE ON BASE BUILDING PLANS AS
 THIS IS SHOWN WITH GFCI PROTECTION WHEN IN FACT THIS IS
 GFP PER 240.13, 230.95.
  
  
 5) NOTE: ELECTRICAL RISER AS SHOWN ON E5.1 IS SHOWN AS
 EXISTING AND IS NOT REVIEWED FOR CODE COMPLIANCE.
 BASE BUILDING IS YET TO RECEIVE CO.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  