| 2008-06-03 18:50:27 | ** DENIED** |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE LIGHTING WHICH IS BEING SHOWN |
| | ON ELECTRICAL LIGHTING PLANS NOTED WITH NOTE #4 SHALL |
| | NOT HAVE PROVISIONS FOR FUTURE LIGHTS. BASED ON THE |
| | METHOD OF CALCULATIONS SUBMITTED ALONG WITH THE MAXIMUM |
| | ALLOWED WATTAGE AS SHOWN THESE LIGHT FIXTURES WOULD |
| | PLACED THE ALLOWANCE WAY OVER THE TABLE ALLOWANCE AND |
| | PERMITTED WATTAGE CONSUMPTION PER 13-415.2.ABC.1.1, |
| | .1.2, 13-415.2.C. |
| | PLEASE ADJUST PLANS AND PLEASE REMOVED FIXTURES. THE |
| | DESIGN OF FIXTURES, NUMBER OF FIXTURES, WATTAGE OF |
| | FIXTURES ETC MAY BE REVISED, HOWEVER MAT NOT BE DONE AS |
| | SHOWN. |
| | PLEASE ALSO KNOW THE *ALTERNATE LIGHTING* SHOWN ON E0.1 |
| | IS NOT PART OF THE DESIGN AT THIS TIME. IF THIS IS |
| | GOING TO BE USED THEN PLANS NEED TO BE REVISED |
| | ACCORDINGLY. |
| | |
| | 2) NOTE: PLEASE VERIFY ACTUAL ROOM DESIGNATION FOR |
| | IT/PHONE ROOM #123. IF THIS IS ACTUALLY AN IT ROOM THEN |
| | PLEASE SHOW COMPLIANCE WITH 645 OF THE NEC. IF THIS NOT |
| | AN IT ROOM PLEASE REMOVE THE IT DESIGNATION. |
| | |
| | 3) NOTE: PLEASE BE SURE ALL CIRCUITING ON PLANS |
| | COORDINATES WITH THE SUBMITTED PANEL SCHEDULES. |
| | PLEASE SUBMIT OTHER PANEL SCHEDULES FOR ITEMS LISTED ON |
| | PLANS, BUT NO SCHEDULE SUBMITTED. |
| | FOR EXAMPLE: |
| | PLEASE SEE ROOM 125, CIRCUIT SHOWN TO PANEL HA-7 YET NO |
| | HA PANEL WAS SUBMITTED. |
| | |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 4) NOTE: REDLINED MDP AS DONE ON BASE BUILDING PLANS AS |
| | THIS IS SHOWN WITH GFCI PROTECTION WHEN IN FACT THIS IS |
| | GFP PER 240.13, 230.95. |
| | |
| | |
| | 5) NOTE: ELECTRICAL RISER AS SHOWN ON E5.1 IS SHOWN AS |
| | EXISTING AND IS NOT REVIEWED FOR CODE COMPLIANCE. |
| | BASE BUILDING IS YET TO RECEIVE CO. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |