| 2008-06-03 09:46:54 | ****CORRECTIONS**** |
| | ****REVISED 6/23/8**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.AS THE BASE BUILDING HAS NOT OBTAINED A C.C. OR |
| | C.O, PLEASE HAVE THE DESIGNER OF THE BASE BUILDING |
| | (SMITH & MOORE) REVIEW THE PLANS.THIS CAN BE DONE |
| | WITH A SHOP DRAWING REVIEW STAMP OR A LETTER. |
| | |
| | 2.GOVERNING CODE, LS1.0, SHOULD INCLUDE 2007 |
| | REVISIONS/SUPPLEMENTS. |
| | |
| | 3.ON THE LIFE SAFETY PLAN, PLEASE SHOW FIRE |
| | RESISTANCE RATING TO THE EXITS ON THE EAST SIDE, |
| | FBC1002.TRAVEL DISTANCE HAS BEEN MEASURED TO THE |
| | DOORS TO THE SPACE, BUT IT IS NOT CLEAR WHERE THE EXIT |
| | DISCHARGE FOR THE NORTH DOOR (FOR THE SPACE, APPARENTLY |
| | LEADING TO THE EAST EXIT).TRAVEL DISTANCE HAS BEEN |
| | SHOWN MEASURED TO THE DOOR TO THE SPACE, BUT FIRE |
| | RESISTANCE RATING TO THE EXIT DISCHARGE HAS NOT BEEN |
| | SHOWN. |
| | |
| | 4.PROVIDE A DETAIL FOR THE ACCESSIBLE SINK, FBC |
| | 11-4.24.PLEASE PROVIDE ALL DIMENSIONS AS REQUESTED BY |
| | THE PLUMBING REVIEWER. |
| | |
| | 5.SUITE 100 IS ALREADY IN USE BY ANOTHER TENANT |
| | (ISSUED PERMIT).PLEASE REVISE SUITE NUMBER ON THE |
| | PLANS AND ON THE APPLICATION. |
| | |