| 2008-06-24 10:05:07 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1. SEE SHEET 1.CONSTRUCTION IS NOT CLEAR.PLANS SHOW |
| | 2X6 WITH 2X2 ?CROSS BEAMS?, THEN STATES THAT THE |
| | LATTICE WILL BE STAPLED EVERY 2IN ALONG EVERY TRUSS AND |
| | CROSS BEAM.IF THE ?CROSS BEAM? SITS ON TOP OF THE |
| | FRAMING, THAT IS NOT POSSIBLE.DO YOU MEAN 2X2 |
| | PURLINS?THIS IS SHOWN GRAPHICALLY AS EITHER SITTING |
| | ON TOP OR THE 2X6S CUT TO FIT IN BETWEEN.THE GRAPHIC |
| | DOES NOT APPEAR TO MATCH THE SPECIFICATION, PLEASE |
| | CLARIFY DETAIL. |
| | |
| | 2. ADDRESSED. |
| | |
| | 3. VALUE HAS BEEN ADJUSTED AS PER MARSHALL & SWIFT, |
| | ADDITIONAL FEES DUE. SEE ATTACHED BILL $55.99. |
| | |
| | 4. ADDRESSED. |
| | |
| | 5.DECLARE GOVERNING CODE, INCLUDING 2007 |
| | REVISIONS/SUPPLEMENTS. |
| | |
| | 2ND REVIEW, NOT ADDRESSED.PLEASE REVISE PLAN TO |
| | INCLUDE GOVERNING CODE WHICH SHOULD STATE:FBC2004 |
| | WITH 2007 REVISIONS/SUPPLEMENTS. |
| | |
| | 6.SHOW COMPLIANCE WITH FBC*109.3.4, TERMITE |
| | PROTECTION. |
| | |
| | 7.SEE FBC106.3.5.4(6), STRUCTURAL REQUIREMENTS, |
| | CONNECTORS NOT SHOWN AT ALL CONNECTIONS.USUALLY A |
| | GRAPHIC IS PLACED ON THE PLAN INDICATING THAT ALL |
| | FRAMING WILL HAVE THE CONNECTOR SPECIFIED; THE PLAN |
| | POINTS TO ONLY ONE PER CONNECTOR.PLEASE REVISE. |
| | |
| | 8.DECLARE WIND DESIGN CRITERIA, FBC R301.THIS |
| | SHOULD INCLUDE WIND SPEED AND EXPOSURE CLASSIFICATION, |
| | IMPORTANCE FACTOR. |
| | |
| | 2ND REVIEW, NOT ADDRESSED.PLEASE REVISE PLAN TO |
| | INCLUDE THIS REQUIRED INFORMATION, WHICH IS MOST LIKELY |
| | 140MPH, EXPOSURE B. |
| | |
| | 9-13. ADDRESSED. |
| | |
| | 14.SHOW GRADE IN RELATION TO THE FINISHED FLOOR, FBC |
| | R312.SHEET 2 STATES THAT THIS WILL BE 36IN, BUT THIS |
| | INFORMATION SHOULD BE INCORPORATED INTO THE PLAN. |
| | |
| | 2ND REVIEW, SHEET 4 SHOWS THIS AS 36IN, BUT SHEET 7 |
| | SHOWS THIS DIMENSION AS 34IN.PLEASE REVISE AND CHECK |
| | ALL (36IN REQUIRED), FBC R 312.1. |
| | |
| | 15.SHEET 8, STAIR DETAIL, FRONT VIEW OF RAILS SHOWS A |
| | 32IN HEIGHT, SIDE VIEW SHOWS 36IN.PLEASE REVISE |
| | DIMENSION FOR FRONT VIEW, FBC R301. |
| | |
| | 16-19. ADDRESSED. |
| | |
| | 20. REGARDING THE STAIR DETAIL PROVIDED ON SHEET 8: |
| | |
| | A. SEE FBCR311.5.3.2, THE SUM OF TWO RISERS AND A TREAD |
| | SHALL NOT BE LESS THAN 24IN NOR MORE THAN 25IN.NOTE |
| | THAT YOU MUST TAKE ACTUAL DIMENSIONS, NOT THE NOMINAL |
| | DIMENSIONS. |
| | |
| | B. CLARIFY RISER HEIGHT.A RISER IS SHOWN AS 5/8X6, |
| | BUT IF A 2X IS PLACED ON TOP, THE RISER HEIGHT IS NOT |
| | 6IN.PROVIDE A DETAIL WHICH IS GRAPHICALLY CORRECT AND |
| | WHICH SHOWS ALL DIMENSIONS, INCLUDING RISER HEIGHT. |
| | COMPLIANCE WITH ITEM 20A CANNOT BE DETERMINED. |
| | |
| | 21-23. ADDRESSED. |
| | |