Plan Review Notes
Plan Review Notes For Permit 08050346
Permit Number 08050346
Review Stop B
Sequence Number 2
Notes
Date Text
2008-06-24 10:05:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1. SEE SHEET 1.CONSTRUCTION IS NOT CLEAR.PLANS SHOW
 2X6 WITH 2X2 ?CROSS BEAMS?, THEN STATES THAT THE
 LATTICE WILL BE STAPLED EVERY 2IN ALONG EVERY TRUSS AND
 CROSS BEAM.IF THE ?CROSS BEAM? SITS ON TOP OF THE
 FRAMING, THAT IS NOT POSSIBLE.DO YOU MEAN 2X2
 PURLINS?THIS IS SHOWN GRAPHICALLY AS EITHER SITTING
 ON TOP OR THE 2X6S CUT TO FIT IN BETWEEN.THE GRAPHIC
 DOES NOT APPEAR TO MATCH THE SPECIFICATION, PLEASE
 CLARIFY DETAIL.
  
 2. ADDRESSED.
  
 3. VALUE HAS BEEN ADJUSTED AS PER MARSHALL & SWIFT,
 ADDITIONAL FEES DUE. SEE ATTACHED BILL $55.99.
  
 4. ADDRESSED.
  
 5.DECLARE GOVERNING CODE, INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  
 2ND REVIEW, NOT ADDRESSED.PLEASE REVISE PLAN TO
 INCLUDE GOVERNING CODE WHICH SHOULD STATE:FBC2004
 WITH 2007 REVISIONS/SUPPLEMENTS.
  
 6.SHOW COMPLIANCE WITH FBC*109.3.4, TERMITE
 PROTECTION.
  
 7.SEE FBC106.3.5.4(6), STRUCTURAL REQUIREMENTS,
 CONNECTORS NOT SHOWN AT ALL CONNECTIONS.USUALLY A
 GRAPHIC IS PLACED ON THE PLAN INDICATING THAT ALL
 FRAMING WILL HAVE THE CONNECTOR SPECIFIED; THE PLAN
 POINTS TO ONLY ONE PER CONNECTOR.PLEASE REVISE.
  
 8.DECLARE WIND DESIGN CRITERIA, FBC R301.THIS
 SHOULD INCLUDE WIND SPEED AND EXPOSURE CLASSIFICATION,
 IMPORTANCE FACTOR.
  
 2ND REVIEW, NOT ADDRESSED.PLEASE REVISE PLAN TO
 INCLUDE THIS REQUIRED INFORMATION, WHICH IS MOST LIKELY
 140MPH, EXPOSURE B.
  
 9-13. ADDRESSED.
  
 14.SHOW GRADE IN RELATION TO THE FINISHED FLOOR, FBC
 R312.SHEET 2 STATES THAT THIS WILL BE 36IN, BUT THIS
 INFORMATION SHOULD BE INCORPORATED INTO THE PLAN.
  
 2ND REVIEW, SHEET 4 SHOWS THIS AS 36IN, BUT SHEET 7
 SHOWS THIS DIMENSION AS 34IN.PLEASE REVISE AND CHECK
 ALL (36IN REQUIRED), FBC R 312.1.
  
 15.SHEET 8, STAIR DETAIL, FRONT VIEW OF RAILS SHOWS A
 32IN HEIGHT, SIDE VIEW SHOWS 36IN.PLEASE REVISE
 DIMENSION FOR FRONT VIEW, FBC R301.
  
 16-19. ADDRESSED.
  
 20. REGARDING THE STAIR DETAIL PROVIDED ON SHEET 8:
  
 A. SEE FBCR311.5.3.2, THE SUM OF TWO RISERS AND A TREAD
 SHALL NOT BE LESS THAN 24IN NOR MORE THAN 25IN.NOTE
 THAT YOU MUST TAKE ACTUAL DIMENSIONS, NOT THE NOMINAL
 DIMENSIONS.
  
 B. CLARIFY RISER HEIGHT.A RISER IS SHOWN AS 5/8X6,
 BUT IF A 2X IS PLACED ON TOP, THE RISER HEIGHT IS NOT
 6IN.PROVIDE A DETAIL WHICH IS GRAPHICALLY CORRECT AND
 WHICH SHOWS ALL DIMENSIONS, INCLUDING RISER HEIGHT.
 COMPLIANCE WITH ITEM 20A CANNOT BE DETERMINED.
  
 21-23. ADDRESSED.
  