| 2008-05-13 15:04:06 | RESIDENTIAL (R3) DOORS AND WINDOWS CHANGE OUT, BUILDING |
| | REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIREDBY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 2- WINDOWS NOA 05-0729.03 SUBMITTED EXPIRED ON JULY 11, |
| | 2007. NEED TO PROVIDE CURRENT PRODUCT APPROVALAS |
| | REQUIRED BY DCA RULE 9B-72. |
| | |
| | 3-A) IF WINDOWSHAVE NOT IMPACT GLASS, THEN NEED TO |
| | PROVIDE PRODUCT APPROVAL FOR TYPE OF STORM SHUTTERS |
| | USED TO PROTECT THE GLAZING AS REQUIRED BY SEC. 507.3 |
| | OF 2004 FLORIDA EXISTING BUILDING CODE. |
| | |
| | B) PROVIDE COMPLETE INSTALLATION SCHEDULE FOR STORM |
| | SHUTTERS. SEE ATTACHED SAMPLE. COMPLETE ALL THE |
| | RELEVANT INFORMATION. |
| | ALSO, CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS (EG: WALL MOUNTED SHUTTERS) AND |
| | ANCHOR TYPE AND SPACING TO BE USED ACCORDING TO THE |
| | DESIGN PRESSURES, EDGE DISTANCE, CONNECTION TYPE, |
| | SHUTTER SPAN AND STRUCTURE TO BE ATTACHED TO (CONCRETE, |
| | CONCRETE BLOCK OR WOOD).SEE SHUTTER DRAWINGS TO FIND |
| | ALL THE INFORMATION. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004 TO VERIFY COMPLIANCE WITH PROPOSED SHUTTERS |
| | INSTALLATION AND DESIGN INFORMATION FROM SEC. R301 OF |
| | 2004 FLORIDA RESIDENTIALCODE. |
| | |
| | 4- SPECIFYTYPE OF EXISTING WINDOWS (EG: SINGLE HUNG |
| | WINDOWS)TO VERIFY COMPLIANCE WITH THE EGRESS |
| | REQUIREMENTS SEC. 501.2 AND SEC. 505 OF 2004 FLORIDA |
| | EXISTING BUILDING CODE. NEED TO VERIFY THAT EGRESS |
| | OPENINGS SIZES ARE NOT LESSSAFE THAN WHENPREVIOUS |
| | WINDOWS WERE INSTALLED. |
| | |
| | 5-PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION |
| | IS TOO LOW.SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | UPDATE VALUATION AS REQUIRED TOINCLUDEALLDOORS |
| | AND WINDOWS TO BE REPLACED AND INSTALLATION OF THE |
| | STORM SHUTTERS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |