| 2008-05-14 17:06:50 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER |
| | 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | |
| | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS |
| | AMENDED. ADJUST THE VALUE AT THE PERMIT CLERK'S DESK, |
| | AND PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. |
| | |
| | 2} PER FS 489 A LICENSED CONTRACTOR IS REQUIRED TO |
| | APPLY FOR THIS PERMIT. |
| | |
| | 3} INDICATE THE MAST AND CONDUCTOR SIZES ON THE RISER |
| | DIAGRAM, SHEET E-1.0. 215.5 2005 NEC. |
| | |
| | 4} NOTE #1, SHEET E-1.0 INCORRECTLY REVERENCES FBC 2004 |
| | (REVISED 2003), SEE REFERENCED STANDARDS 2007 |
| | REVUSIONS. |
| | |
| | 5} THE SMOKE DETECTOR CONNECTION DETAIL (ALSO SEE THE |
| | DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72, |
| | CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID |
| | CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE |
| | LOCATIONS OF THE SOUNDING DEVICES) DETAIL INDICATES |
| | KITCHEN OR BATH CIRCUIT FEED, SEE 210.12 FOR AFCI |
| | REQUIREMENTS. |
| | |
| | 6} PANEL "B" HAS CIRCUITS MISLABELED AS "A". |
| | |
| | 7} LOCATE AND INDICATE A DISCONNECTING MEANS FOR THE |
| | WATER HEATER. SEE 422.16 NEC FOR CORD AND PLUG |
| | RESTRICTIONS, AND 422.31(B) FOR HARDWIRE REQUIREMENTS. |
| | |
| | 8} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14,RECEPTACLE PER 210.63. |
| | |
| | 9} 210.11(C)(1) SMALL-APPLIANCE BRANCH CIRCUITS IN |
| | ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| | OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE |
| | SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR |
| | ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B). |
| | |
| | 10} 21.52(C)(1) WALL COUNTER SPACES A RECEPTACLE OUTLET |
| | SHALL BE INSTALLED AT EACH WALL COUNTER SPACE THAT IS |
| | 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE |
| | INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE |
| | THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A |
| | RECEPTACLE OUTLET IN THAT SPACE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |