Plan Review Notes
Plan Review Notes For Permit 08050249
Permit Number 08050249
Review Stop E
Sequence Number 2
Notes
Date Text
2008-07-03 15:38:07 
 ** DENIED AUDIT**
  
 1) NOTE:PLEASE SEE AS STATED ON PREVIOUS REVIEW
 PLEASE ONLY SUBMIT PLANS FOR APPLIED SCOPE OF WORK.
 AS EACH PROJECT IS A SEPARATE LEGAL RECORD SET OF
 PLANS, CONDUITS AND SIZES FOR SERVICE ETC ARE REQUIRED
 IN EACH SET OF PLANS FOR EACH PROJECT.
 PLEASE INCLUDE CONDUITS FOR RISER/UNDERGROUND.
  
 2) NOTE: SHEET E109C INDICATES A SUBSTANTIAL GROUNDING
 SYSTEM HOWEVER COULD NOT LOCATE THE MINIMUM ITEMS
 REQUIRED BY 250.50.
 PLEASE PROVIDE GROUNDING ELECTRODE RISER. COULD NOT
 LOCATE FOOTER STEEL, COLD WATER PIPE, ETC.
 250.50, 250.53, 250.58 ETC
  
 3) NOTE: PLEASE SEE FS553.791. PLEASE PROVIDE THE
 COMPLIANCE AFFIDAVIT FOR EACH TRADE LISTING THE SHEETS
 ON SAID AFFIDAVIT. LISTING SEE ATTACHED DOES MEET THE
 INTENT OR REQUIREMENT OF STATUTE.
 ANY ATTACHED SHEET COULD LIST ANY ITEM IN WHICH THE
 AFFIDAVIT MAY OR MAY NOT HAVE BEEN SIGNED FOR
 CERTIFYING COMPLIANCE.
 THIS HAS BEEN CONFIRMED WITH BUILDING OFFICIAL AND ASST
 BUILDING OFFICIAL.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II