| Date |
Text |
| 2008-07-03 15:38:07 | |
| | ** DENIED AUDIT** |
| | |
| | 1) NOTE:PLEASE SEE AS STATED ON PREVIOUS REVIEW |
| | PLEASE ONLY SUBMIT PLANS FOR APPLIED SCOPE OF WORK. |
| | AS EACH PROJECT IS A SEPARATE LEGAL RECORD SET OF |
| | PLANS, CONDUITS AND SIZES FOR SERVICE ETC ARE REQUIRED |
| | IN EACH SET OF PLANS FOR EACH PROJECT. |
| | PLEASE INCLUDE CONDUITS FOR RISER/UNDERGROUND. |
| | |
| | 2) NOTE: SHEET E109C INDICATES A SUBSTANTIAL GROUNDING |
| | SYSTEM HOWEVER COULD NOT LOCATE THE MINIMUM ITEMS |
| | REQUIRED BY 250.50. |
| | PLEASE PROVIDE GROUNDING ELECTRODE RISER. COULD NOT |
| | LOCATE FOOTER STEEL, COLD WATER PIPE, ETC. |
| | 250.50, 250.53, 250.58 ETC |
| | |
| | 3) NOTE: PLEASE SEE FS553.791. PLEASE PROVIDE THE |
| | COMPLIANCE AFFIDAVIT FOR EACH TRADE LISTING THE SHEETS |
| | ON SAID AFFIDAVIT. LISTING SEE ATTACHED DOES MEET THE |
| | INTENT OR REQUIREMENT OF STATUTE. |
| | ANY ATTACHED SHEET COULD LIST ANY ITEM IN WHICH THE |
| | AFFIDAVIT MAY OR MAY NOT HAVE BEEN SIGNED FOR |
| | CERTIFYING COMPLIANCE. |
| | THIS HAS BEEN CONFIRMED WITH BUILDING OFFICIAL AND ASST |
| | BUILDING OFFICIAL. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |