| Date |
Text |
| 2008-05-23 16:57:02 | AUDIT DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS A001C, A101C, A102C, & A901C ARE NOT SIGNED, |
| | SEALED & DATED OR REVIEWED BY THE PRIVATE PROVIDER AS |
| | REQUIRED BY FAC 61G15-23.002(2) & FS 471.2055, FS |
| | 553.791. |
| | |
| | 2. PLEASE SUBMIT COMPLETED AFFIDAVITS AS REQUIRED PER |
| | FS 553.791. |
| | |
| | 3. ALL SHEETS WITH WBCM CONSULTING ENGINEER TITLE BLOCK |
| | SHALL ALSO INDICATE THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER ON EACH SHEET. FAC 61G15-23.002(2) & FS |
| | 471.2055. |
| | |
| | 4.ALL "C" SHTS, "S" SHTS, "M" SHTS & "E" SHTS. THE |
| | PRINTED NAME AND THE LICENSE NUMBER OF THE PERSON |
| | SEALING THE DOCUMENT SHALL BE INDICATED ON EACH SHEET. |
| | FAC 61G15-23.002(2) & FS 471.2055. |
| | |
| | 5.ALL PLMG SHTS. THE SIGNATURE OF THE PERSON SEALING |
| | THE DOCUMENT IS REQUIRED. IT APPEARS THAT INITIALS HAVE |
| | BEEN USED TO SIGN THE PLANS. IF THIS IS INDEED THE |
| | LEGAL SIGNATURE OF THE ENGINEER, THEN PLEASE SUBMIT A |
| | SIGNED, SEALED, DATED NOTORIZED LETTER INDICATING THE |
| | LEGAL SIGNATURE OF THE ENGINEER FOR OUR FILES. FAC |
| | 61G15-23.002(1)(2) & FS 471.2055. |
| | |
| | 6. SHT P104C RISER W/3PLEASE SHOW PIPING TO EWH-2 |
| | WITH FULL OPEN VALVE REQUIRED PER SECTION 606.1(7) AND |
| | THE HOT WATER PIPING TO LAV-2 AS WELL AS THE SHUT OFF |
| | VALVE TO THE HOSE BIBB AS REQUIRED BY SECTION 606.2(2) |
| | ON THE RISER DIAGRAM. |
| | |
| | 7. SHT P104C RISER W/1 RISER PIPE SIZES DO NOT REFLECT |
| | THE FLOOR PLAN. FLOOR PLAN SHOWS 1" DROP TO URINAL & |
| | 3/4" TO THE LAV. THE RISER SHOWS 1-1/4" TO THE URINAL |
| | AND 1/2" TO THE LAV. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 8. SHT P104C DETAILS FOR INSTANTANEOUS WATER HEATERS. |
| | PER SECTION 606.1(7)FULL OPEN VALVES ARE REQUIRED ON |
| | THE SUPPLY PIPING TO THE WATER HEATERS. PLEASE INDICATE |
| | ON DETAIL. |
| | |
| | 9. SHT P104C THERE IS NO SANITARY RISER DIAGRAM FOR THE |
| | DRINKING FOUNTAIN AT THE MEZZ. LEVEL. THIS WILL BE |
| | REQUIRED WHEN SUBMITTING FOR BUILDING PERMIT. |
| | (INFORMATIONAL) |
| | |
| | 10. NO STORM PIPING FROM THE ROOF IS INDICATED ON THE |
| | PLUMBING PLANS. IF THERE ARE ROOF DRAINS AND RELATED |
| | PIPING UNDERGROUND THE PIPING SHALL BE SHOWN WITH STORM |
| | ISOMETRIC RISER DIAGRAMS. SECTION 106.3.5.1.3. |
| | |
| | 11. ALL ACCESSIBILITY REQUIREMENTS FOR THE TOILET ROOMS |
| | ARE REQUIRED. (INFORMATIONAL). ALL FOUNDATION WORK IS |
| | AT CONTRACTORS OWN RISK. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |