| 2008-05-22 08:27:59 | ** DENIEDAUDIT** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETED AFFIDAVITS AS REQUIRED |
| | PER FS 553.791. |
| | PLEASE SEE THE ONE ELECTRICAL SHEET IS LISTED HOWEVER |
| | NO DATES FOR WHEN PLANS WERE SIGNED, DATED AND SEALED. |
| | |
| | 2) NOTE: PLEASE SEE THE TITLE BLOCKS ON ELECTRICAL |
| | SHEETS AS WELL AS TITLE BLOCKS ON OTHER PLANS ARE |
| | MISSING THE REQUIRED INFORMATION PER FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002. |
| | PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER |
| | OF THE DESIGNER. |
| | PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER |
| | FOR FIRMS SUCH AS *GIPE ASSOCIATES INC*, WHITNEY, |
| | BAILEY, COX AND MAGNANI LLC* ETC. |
| | PLEASE SEE FLORIDA STATUTES 471.023 FOR ENGINEERING |
| | FIRMS AND 481.219 FOR ARCHITECTURAL FIRMS. |
| | ** THIS COMMENT IS FOR ALL TRADES AND FOR ALL |
| | REVIEWER(S) WHETHER OR NOT COMMENT IS MADE BY THOSE |
| | OTHER TRADE REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SUBMIT ONLY PLANS RELEVANT TO THE |
| | APPLIED FOUNDATION ELECTRICAL SCOPE OF WORK. PLANS DO |
| | NOT SHOW ANY GROUNDING ELECTRODE SYSTEM AS REQUIRED PER |
| | 250.50. PLEASE SEE THAT PLANS DO NOT SHOW ANY |
| | FOUNDATION PIPING FOR SERVICE, ETC. |
| | PLEASE SUBMIT. |
| | FBC 106.1.2, 106.1, 106.3.5.1.2. ADMIN SECTION FOR |
| | ADDITIONAL INFORMATION AND COORDINATION. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |