Plan Review Notes
Plan Review Notes For Permit 08050249
Permit Number 08050249
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-16 16:16:58****PRIVATE PROVIDER AUDIT****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PLEASE NOTE THAT SOME ITEMS ON THIS LIST AREA
 ADVISORY ONLY TO HELP EXPEDITE THE FUTURE BUILDING
 PERMIT.
  
 2.FBC*105.13, PHASED PERMIT APPROVAL, THE HOLDER OF
 SUCH PERMIT FOR THE FOUNDATIONS OR OTHER PARTS OF A
 BUILDING OR STRUCTURE SHALL PROCEED AT THE HOLDER?S OWN
 RISK WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE
 THAT A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
 CORRECTIONS MAY BE REQUIRED TO MEET THE REQUIREMENTS OF
 THE TECHNICAL CODES.
  
 THIS PERMIT WILL BE ISSUED AT RISK.
  
 3.SEE FAC61G15-23.002, ALL INFORMATION REQUIRED BY
 THIS SECTION IS REQUIRED ON EACH SHEET (PRINTED NAME
 AND LICENSE NUMBER OF THE PERSON SEALING THE DOCUMENT,
 CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING
 FIRM).
  
 4.SEE FS553.791.PROVIDE THE ACKNOWLEDGMENT FROM THE
 OWNER.
  
 5.PLEASE INCLUDE THE DATE OF THE PLAN (OR REVISION
 NUMBER) ON THE PRIVATE PROVIDER PLAN COMPLIANCE
 AFFIDAVIT.
  
 6.THE ATTACHMENT FOR THE PRIVATE PROVIDER PLAN
 COMPLIANCE AFFIDAVIT HAS ENERGY CALCS AND PRODUCT
 APPROVALS CHECKED OFF, BUT NEITHER WAS SUBMITTED.
  
 7.PLEASE NOTE THAT THE PRIVATE PROVIDER AFFIDAVIT IS
 CHECKED (FOR EACH SHEET NUMBER) PRIOR TO PERMIT
 ISSUANCE.PLEASE CONFIRM THAT THE AFFIDAVIT REFERS TO
 ALL SHEETS PRIOR TO RESUBMITTAL.
  
 8.THE FOUNDATION PLAN, S103C, DETAILS REFER TO SHEETS
 S103 THROUGH S109 (EXAMPLE) BUT THE DETAILS THEMSELVES
 ARE ON SHEETS S103C.PLEASE REVISE SO THAT CORRECT
 PAGE NUMBERS ARE REFERENCED, ESPECIALLY AS THE BUILDING
 PLAN WILL MOST LIKELY BE LARGE.
  
 9. I WAS UNABLE TO LOCATE INFORMATION IN REGARDS TO
 TERMITE TREATMENT OF FILL; THIS WAS ALSO NOT NOTED IN
 DETAILS, FOR INSTANCE, 3S104 (LOCATED ON SHEET S104C),
 GENERAL NOTES, NOTES ON S113C.SEE FBC*109.3.4. PLEASE
 REVISE PLAN TO INCLUDE THIS REQUIREMENT.
  
 10. ARCHITECTURAL SHEETS WHICH WERE NOT SIGNED, SEALED,
 AND DATED WERE SUBMITTED.SEE FS481, DOCUMENTS
 PREPARED BY AN ARCHITECT AND SUBMITTED FOR PUBLIC
 RECORD ARE REQUIRED TO BE SIGNED, SEALED, DATED
 ORIGINALS.IF THE PLANS ARE REQUIRED FOR CODE
 COMPLIANCE, THEY MUST SE SIGNED, SEALED, AND DATED.IF
 THEY ARE NOT REQUIRED, THEY MAY BE REMOVED FROM THE
 PERMIT PACKAGE.THE FIRST FLOOR PLAN SHOULD BE
 INCLUDED FOR COORDINATION WITH THE STRUCTURAL PLANS.
  
 11.IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE PLANS MUST BE STAMPED AND THE RECEIPT ATTACHED TO
 THE APPLICATION.I HAVE PLACED A CALL TO PBC TO
 DETERMINE REQUIREMENTS FOR THIS PROJECT, IF ANY.
 561-233-5025.
  
 12. FBC* 109.3.7, A RESIDENT INSPECTOR WILL BE REQUIRED
 TO SUPERVISE THE INSTALLATION OF THE STEEL STRUCTURE.
 THIS COMMENT DOES NOT AFFECT THIS PERMIT AT THIS TIME;
 THIS IS ADVISORY ONLY.THREE SETS WILL BE REQUIRED
 WHEN BUILDING PERMIT APPLICATION IS MADE.
  
 13. THIS PERMIT WAS SUBMITTED AS A FOUNDATION PERMIT
 ONLY.THEREFORE, A COMPLETE PLAN REVIEW OF OTHER
 SHEETS HAS NOT BEEN DONE AT THIS TIME, SUCH AS LIFE
 SAFETY, ACCESSIBILITY, ETC.AS NOTED, THIS PERMIT WILL
 BE ISSUED AT RISK.
  
 14. FIRE SPRINKLER PLANS WILL BE REQUIRED WITH THE
 BUILDING PLANS, FBC*106.3.5.1.1(5), FS553.79 (2).
 INFORMATIONAL ONLY; THIS ISSUE DOES NOT AFFECT THIS
 PERMIT.
  
 15. A901C, OCCUPANCY WAS DETERMINED BASED ON 300SF PER
 OCCUPANT.SEE FBC1004.1; EACH AREA IS TO HAVE AN
 OCCUPANCY LOAD DECLARED BASED ON USE OF THAT AREA.A3
 DECLARED, MUST USE AN OCCUPANT LOAD NOT LESS THAN FBC
 TABLE 1004.1.2.THE LIFE SAFETY PLAN MAY BE REMOVED AS
 THIS WILL NOT BE INCLUDED IN THIS PERMIT.IF INCLUDED,
 PLEASE REVISE OCCUPANT LOAD.
  
 16.S1 OCCUPANCY WAS DECLARED ON A901C, BUT THIS
 APPEARS TO BE FACTORY OCCUPANCY FBC306.
  
 17.S101C, SEVERAL LOCATIONS AND POSSIBLY OTHER
 SHEETS, PLEASE REVISE GOVERNING CODE TO INCLUDE 2007
 REVISIONS/SUPPLEMENTS.CHECK ALL AS OTHER SHEETS MAY
 BE AFFECTED.
  
 18. S101C, 1.C, STATES MAX WIND UPLIFT PRESSURE, 57PSF.
 PLEASE CLARIFY SPECIFICALLY WHAT THIS PRESSURE; MWFRS,
 C&C, ETC.?ANY DESIGN CRITERIA WHICH DOES NOT RELATE
 SPECIFICALLY TO THE FOUNDATION AND SLAB DESIGN MAY BE
 REMOVED.
  
 19. A101C, OTHER SHEETS, A MEZZANINE IS SHOWN.SEE
 FBC505.COMPLIANCE WITH ALL REQUIREMENTS SHALL BE
 REQUIRED TO BE SHOWN ON THE PLAN AT TIME OF BUILDING
 PERMIT REVIEW, OR COMPLIANCE AS A SECOND STORY WILL BE
 REQUIRED.INFORMATIONAL ONLY.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved