| Plan Review Notes For Permit 08050224 |
| Permit Number |
08050224 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-11-01 07:40:20 | | | | | | | DENIED | | | | | | THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE 1ST | | | REVIEW | | | | | | C) IN THE PANEL MOUNTING TYPE COLUMN YOU SHOULD ENTER | | | THE MOUNTING METHOD USED (PAGES 3,4 & 5) NOT THE PARTS | | | FROM PAGE 1A, PLEASE NOTE THAT THESE MOUNTING METHODS | | | ARE IN THE LAST COLUMNS OF THE O/C SPACING TABLES | | | ********PLEASE NOTE THAT PARTS 3, 7 AND 10 ARE ALL PART | | | OF MOUNTING METHOD FOR SECTION 2, THEREFORE 2 WOULD BE | | | USED FOR THE TOP OR BOTTOM IN THE SCEDULE. LIKEWISE IF | | | YOU WERE TO USE PART 10 ON THE BOTTOM SECTION 1 WOULD | | | APPLY. THE SHEDULE MUST BE ACCURATE AND LEGIBLE BECAUSE | | | ONCE CHECKED BY PLAN REVIEW IT WILL BE USED BY THE | | | INSPECTOR ON SITE.******** | | | | | | D) THE SAME IDEA APPLIES TO THE ACCORDION SHUTTERS FOR | | | MOUNTING TYPE (SEE PAGE 5) IF 2 AND 4 ARE CHOSEN ONLY | | | COLUMNS 2 AND 4 ON SHEET 10 WOULD APPLY, THEREFORE THE | | | O/C SPACING FOR SHUTTERS 11 AND 12 WHICH ARE OVER 7'-0" | | | SPAN WOULD BE 7.5" | | | ********THE PRODUCT APPROVALS FOR THE ACCORDIAN | | | SHUTTERS WAS NOT RETURNED WITH THE PERMIT | | | APPLICATION********* | | | | | | 2) SUBMIT 2 COPIES OF CORRECTED SHUTTER SCHEDULE | | | ********ONLY ONE COPY OF THE SHUTTER SCHEDULE WAS | | | SUBMITTED WITH THE PERMIT APPLICATION, PLEASE MAKE ALL | | | CORRECTIONS AND SUBMIT 2 COPIES******** | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | |
|