Plan Review Notes
Plan Review Notes For Permit 08050224
Permit Number 08050224
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-15 15:11:01 
  
 DENIED
  
 1) PLEASE MAKE THE FOLLOWING CORRECTIONS TO THE SHUTTER
 SCHEDULE
  
 A) THE EDGE DISTANCE FOR BOTH THE ACCORDIONS AND THE
 PANELS IS 3 1/2" FOR THE MAXIMUM ON CENTER SPACING
 SHOWN, IF E.D. IS SMALLER PLEASE NOTE THE TABLES ON
 PAGES 6 & 7 OF THE PANEL DRAWINGS AND PAGE 11 OF THE
 ACCORDIONS. SMALLER EDGE DISTANCE REQUIRES THE O/C
 SPACING TO BE MULTIPLIED BY THE FACTOR IN THESE TABLES
 WHICH IN TURN WILL ADJUST THE SPACING DISTANCE. UNDER
 NO CIRCUMSTANCE CAN 1" BE USED AS STATED IN YOUR
 SCHEDULE, THE MINIMUM EDGE DISTANCE IS 2".
  
 B) PANEL LENGTHS ON AVERAGE ARE OPENING WIDTH OR HEIGHT
 PLUS EDGE DISTANCE X 2, (7") PLUS APPROX 2" FOR PANEL
 PAST THE MOUNTING SCREW
  
 C) IN THE PANEL MOUNTING TYPE COLUMN YOU SHOULD ENTER
 THE MOUNTING METHOD USED (PAGES 3,4 & 5) NOT THE PARTS
 FROM PAGE 1A, PLEASE NOTE THAT THESE MOUNTING METHODS
 ARE IN THE LAST COLUMNS OF THE O/C SPACING TABLES
  
 D) THE SAME IDEA APPLIES TO THE ACCORDION SHUTTERS FOR
 MOUNTING TYPE (SEE PAGE 5) IF 2 AND 4 ARE CHOSEN ONLY
 COLUMNS 2 AND 4 ON SHEET 10 WOULD APPLY, THEREFORE THE
 O/C SPACING FOR SHUTTERS 11 AND 12 WHICH ARE OVER 7'-0"
 SPAN WOULD BE 7.5"
  
 E) SHUTTER PANEL FOR OPENING # 2 WHEN PANEL LENGTH IS
 CORRECTED PER FORMULA IN NOTE "A" EXCEEDS THE MAXIMUM
 PANEL LENGTH ALLOWED PER TABLE ON SHEET 5 IF H HEADER
 IS USED, BUT WOULD BE ALRIGHT IF DIRECT MOUNTED TO
 WALL
  
 F) PLEASE SEE NOTE ON PAGE 5 OF PANEL DRAWINGS, 3'-0"
 IS MINIMUM PANEL LENGTH THEREFORE OPENING # 14 PANELS
 ARE REQUIRED TO BE LENGTHENED OR INSTALLED
 HORIZONTALLY
  
 2) SUBMIT 2 COPIES OF CORRECTED SHUTTER SCHEDULE
  
 3) MAKE CORRECTIONS TO DRAWINGS THAT REFLECT THE WORK
 TO BE PERFORMED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  