| Plan Review Notes For Permit 08050216 |
| Permit Number |
08050216 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-09-03 14:18:55 | 2004 FBC W/2007 REVISIONS | | | METAL SHELTER | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE METAL | | | ROOF COVERING WITH ADEQUATE DESIGN PRESSURES. TWO | | | COPIES OF THE EVALUATION REPORT WITH DESIGN PRESSURE | | | SPECIFIED AND INSTALLATION INSTRUCTIONS ARE REQUIRED. | | | SEE FAC RULE 9B-72 AND FBC 106.1* CITY AMENDMENTS. THE | | | STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND HAS A | | | 4:12 ROOF SLOPE, WHICH REQUIRES A ROOFING PRODUCT WITH | | | A DESIGN PRESSURE CAPABLE OF RESISTING AN UPLIFT OF | | | 100.5 PSF AT ROOF ZONE 3. SEE FBC TABLES 1609.6.2.1(2) | | | AND 1609.6.2.1(4). REPEAT COMMENT. | | | | | | 2) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | REPEAT COMMENT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|