Plan Review Notes
Plan Review Notes For Permit 08050216
Permit Number 08050216
Review Stop B
Sequence Number 2
Notes
Date Text
2008-07-28 14:35:062004 FBC W/2007 REVISIONS
 METAL SHELTER
  
 DENIED BY BUILDING
  
 1) THE SET-UP INSTRUCTIONS SPECIFY THE ROOF PANELS AS
 24 GA. MEDALLION-LOK STEEL PANELS MANUFACTURED BY
 MCELROY METAL, INC. THERE WERE NO PRODUCT APPROVALS FOR
 THE ROOF PANELS SUBMITTED AS REQUESTED IN ITEM #4 OF
 THE PREVIOUS PLAN REVIEW. THEREFORE, THE MIAMI-DADE
 EVALUATION REPORT AND INSTALLATION INSTRUCTIONS FOR
 THIS PRODUCT (NOA NO. 08-0225.03) WAS USED TO DETERMINE
 THE DESIGN PRESSURES FOR THE METAL ROOF. THE MAXIMUM
 DESIGN PRESSURE FROM THE NOA IS -71.25 PSF, WITH NO
 EXTRAPOLATION ALLOWED. THIS DESIGN PRESSURE IS NOT
 ADEQUATE TO RESIST THE REQUIRED UPLIFT FOR COMPONENT
 AND CLADDING FOR A 4:12 SLOPE ROOF IN EXPOSURE CATEGORY
 C. SEE FBC TABLE 1609.6.2.1(2) AND ADJUSTMENT FACTORS
 TABLE 1609.6.2.1(4). PLEASE PROVIDE PRODUCT APPROVALS
 FOR ROOF COVERING WITH ADEQUATE DESIGN PRESSURES. SEE
 DCA RULE 9B-72.
  
 2) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 SEE PREVIOUS REVIEW COMMENT # 5.
  