Plan Review Notes
Plan Review Notes For Permit 08050211
Permit Number 08050211
Review Stop M
Sequence Number 1
Notes
Date Text
2008-05-23 15:20:54REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 COMMENTS:
 1. PG A-2 AND M-2: SUITE #155 IS BEING SEPARATED FROM
 THE CENTRALIZED RETURN AIR INTAKE BY FULL-HEIGHT RATED
 PARTITIONS. NO PROVISIONS ARE SHOWN ON PLANS FOR THE
 FLOW OF RETURN AIR ABOVE THE CEILING PLENUM BACK TO THE
 A/C SYSTEM SHOW HOW BALANCED RETURN IS TO BE ACHIEVED
 IN THIS AREA IN ACCORDANCE WITH FBCM 601.4.
  
 2. SEVERAL SPACES IN THE WORK AREA ARE BEING
 RECONFIGURED. ALL RECONFIGURED SPACES INTENDED FOR
 OCCUPANCY IN ANY WORK AREA SHALL BE PROVIDED WITH
 NATURAL OR MECHANICAL VENTILATION IN ACCORDANCE WITH
 FBCEB 609.1 AND FBCM 401.2. PROVIDE OUTSIDE AIR
 CALCULATIONS SHOWING REQUIRED VENTILATION RATES FOR
 SPACES. VERIFY EXISTING SYSTEM IS CAPABLE OF PROVIDING
 THE REQUIRED VENTILATION AND PROVIDE INFORMATION ON HOW
 SYSTEMS IS TO BE REBALANCED, IF REQUIRED, TO
 DEMONSTRATE COMPLIANCE WITH THESE SECTIONS.
 NOTE: THE LOBBY/RECEPTION AREA IN SUITE #155 MAY HAVE
 HIGHER VENTILATION RATE REQUIREMENTS THAN THE
 PREVIOUSLY EXISTING OPEN WORK AREAS AT THE SAME
 LOCATION IN ACCORDANCE WITH FBCM TABLE 403.3.
  
 NOTE: ENERGY CALCULATIONS WERE NOT REVIEWED FOR THE
 MECHANICAL PROVISIONS OF THE FLORIDA ENERGY EFFICIENCY
 CODE AS THERE ARE NO NEW AIR CONDITIONING SYSTEMS BEING
 INSTALLED. ONLY COMPLIANCE WITH FBCB 13-101.6 IS
 REQUIRED.
  