| 2008-05-23 15:20:54 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | COMMENTS: |
| | 1. PG A-2 AND M-2: SUITE #155 IS BEING SEPARATED FROM |
| | THE CENTRALIZED RETURN AIR INTAKE BY FULL-HEIGHT RATED |
| | PARTITIONS. NO PROVISIONS ARE SHOWN ON PLANS FOR THE |
| | FLOW OF RETURN AIR ABOVE THE CEILING PLENUM BACK TO THE |
| | A/C SYSTEM SHOW HOW BALANCED RETURN IS TO BE ACHIEVED |
| | IN THIS AREA IN ACCORDANCE WITH FBCM 601.4. |
| | |
| | 2. SEVERAL SPACES IN THE WORK AREA ARE BEING |
| | RECONFIGURED. ALL RECONFIGURED SPACES INTENDED FOR |
| | OCCUPANCY IN ANY WORK AREA SHALL BE PROVIDED WITH |
| | NATURAL OR MECHANICAL VENTILATION IN ACCORDANCE WITH |
| | FBCEB 609.1 AND FBCM 401.2. PROVIDE OUTSIDE AIR |
| | CALCULATIONS SHOWING REQUIRED VENTILATION RATES FOR |
| | SPACES. VERIFY EXISTING SYSTEM IS CAPABLE OF PROVIDING |
| | THE REQUIRED VENTILATION AND PROVIDE INFORMATION ON HOW |
| | SYSTEMS IS TO BE REBALANCED, IF REQUIRED, TO |
| | DEMONSTRATE COMPLIANCE WITH THESE SECTIONS. |
| | NOTE: THE LOBBY/RECEPTION AREA IN SUITE #155 MAY HAVE |
| | HIGHER VENTILATION RATE REQUIREMENTS THAN THE |
| | PREVIOUSLY EXISTING OPEN WORK AREAS AT THE SAME |
| | LOCATION IN ACCORDANCE WITH FBCM TABLE 403.3. |
| | |
| | NOTE: ENERGY CALCULATIONS WERE NOT REVIEWED FOR THE |
| | MECHANICAL PROVISIONS OF THE FLORIDA ENERGY EFFICIENCY |
| | CODE AS THERE ARE NO NEW AIR CONDITIONING SYSTEMS BEING |
| | INSTALLED. ONLY COMPLIANCE WITH FBCB 13-101.6 IS |
| | REQUIRED. |
| | |