Plan Review Notes
Plan Review Notes For Permit 08050211
Permit Number 08050211
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-27 11:15:45** DENIED REVIEW **
  
 1) NOTE: PLEASE LABEL SUITE/UNITS ON RISER TENANT
 MAINS.
 230.2E.
  
 2) NOTE: PLEASE VERIFY HOW METHOD *C* IS BEING USED
 WHEN NOT PLACING ALL INFORMATION IN THE INPUT DATA
 REPORT FOR ALL AREAS OF SPACES.
 FOR EXAMPLE:
 PLANS SHOW TWO SUITES/UNITS AND YET THE IDR DOES NOT
 CONTAIN ALL AREAS ROOMS FROM THE PLANS?
 PLEASE SEE SQUARE FEET ON THE CALCULATIONS INDICATE
 BOTH SPACES YET THE LIGHTING ON THE IDR DOES NOT
 INCLUDE BOTH.
 BASED ON THE LIGHTING ON PLANS THE MAXIMUM WATTAGE
 APPEARS IT WILL EXCEED TABLE *C*.
 PLEASE ALSO SEE ONE ROOM FOR EXAMPLE IN SUITE #150:
 OFFICE 104, WELL EXCEEDS THE ALLOWANCES OF TABLE
 13-415.2.C FOR OFFICE AREAS.
 ** PLEASE ADJUST FIXTURE TYPES, WATTAGES ETC IN ORDER
 TO BE BELOW. PLEASE KNOW IN ORDER TO ADD OR CONTAIN
 LIGHTING IN ADDITION TO OTHER EXISTING AREAS, IT MAY BE
 REQUIRED TO CHANGE OTHER FIXTURES OR PERHAPS MINIMUM
 FOR SPACE BY SPACE.
 13-415.2.ABC.1.1, .1.2
 ** PLEASE BE SURE THE OWNER AGENT IS FILLED OUT ON THE
 CERTIFICATION SHEET.
  
 3) NOTE: PLEASE LIST THE MAXIMUM TIMES ON OCCUPANCY
 SENSOR DEVICES.
 13-415.1.ABC.1.1,.1.2.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved