| Date |
Text |
| 2008-05-27 11:15:45 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE LABEL SUITE/UNITS ON RISER TENANT |
| | MAINS. |
| | 230.2E. |
| | |
| | 2) NOTE: PLEASE VERIFY HOW METHOD *C* IS BEING USED |
| | WHEN NOT PLACING ALL INFORMATION IN THE INPUT DATA |
| | REPORT FOR ALL AREAS OF SPACES. |
| | FOR EXAMPLE: |
| | PLANS SHOW TWO SUITES/UNITS AND YET THE IDR DOES NOT |
| | CONTAIN ALL AREAS ROOMS FROM THE PLANS? |
| | PLEASE SEE SQUARE FEET ON THE CALCULATIONS INDICATE |
| | BOTH SPACES YET THE LIGHTING ON THE IDR DOES NOT |
| | INCLUDE BOTH. |
| | BASED ON THE LIGHTING ON PLANS THE MAXIMUM WATTAGE |
| | APPEARS IT WILL EXCEED TABLE *C*. |
| | PLEASE ALSO SEE ONE ROOM FOR EXAMPLE IN SUITE #150: |
| | OFFICE 104, WELL EXCEEDS THE ALLOWANCES OF TABLE |
| | 13-415.2.C FOR OFFICE AREAS. |
| | ** PLEASE ADJUST FIXTURE TYPES, WATTAGES ETC IN ORDER |
| | TO BE BELOW. PLEASE KNOW IN ORDER TO ADD OR CONTAIN |
| | LIGHTING IN ADDITION TO OTHER EXISTING AREAS, IT MAY BE |
| | REQUIRED TO CHANGE OTHER FIXTURES OR PERHAPS MINIMUM |
| | FOR SPACE BY SPACE. |
| | 13-415.2.ABC.1.1, .1.2 |
| | ** PLEASE BE SURE THE OWNER AGENT IS FILLED OUT ON THE |
| | CERTIFICATION SHEET. |
| | |
| | 3) NOTE: PLEASE LIST THE MAXIMUM TIMES ON OCCUPANCY |
| | SENSOR DEVICES. |
| | 13-415.1.ABC.1.1,.1.2. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |