Plan Review Notes
Plan Review Notes For Permit 08050194
Permit Number 08050194
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-05-23 16:50:36*****UNSAT*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH ACCESS TO AND/OR EGRESS FROM THE SAID PROPERTY OR
 OTHER TENANT SPACES IN THE VICINITY THEREOF.
  
 4.SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) WHICH
 SATISFY THE 75' TRAVEL DISTANCE.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A
 RESPONSE LETTER INDICATING WHERE THE COMMENT HAS BEEN
 ADDRESSED
  
  
 CAPT. MICHAEL A.WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722