| Plan Review Notes For Permit 08050194 |
| Permit Number |
08050194 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-23 16:50:36 | *****UNSAT***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE | | | WITH ACCESS TO AND/OR EGRESS FROM THE SAID PROPERTY OR | | | OTHER TENANT SPACES IN THE VICINITY THEREOF. | | | | | | 4.SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) WHICH | | | SATISFY THE 75' TRAVEL DISTANCE. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A | | | RESPONSE LETTER INDICATING WHERE THE COMMENT HAS BEEN | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A.WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|