Plan Review Notes
Plan Review Notes For Permit 08050177
Permit Number 08050177
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-07 16:58:23RESIDENTIAL (R3) SHUTTERS AND WINDOW INSTALLATION,
 BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE PRODUCT APPROVAL FOR WINDOW AS REQUIRED BY
 DCA RULE 9B-72. PROVIDE 2 COPIES.
  
 2- PRODUCT APPROVAL SUBMITTED FOR STORM SHUTTERS IS
 EXPIRED. NOA 03-0417.02 SUBMITTED EXPIRED ON 04/21/08.
 NEED TO PROVIDE CURRENT PRODUCT APPROVAL AS REQUIRED BY
 DCA RULE 9B-72.
  
 3- COMPLETE INFORMATION ON INSTALLATION SCHEDULE.
 PROVIDE THE FOLLOWING INFORMATION:
  
 A) SPECIFYOPENING DESIGN PRESSURES. SEE TABLE
 R301.2(2) OF 2004 FLORIDA RESIDENTIAL CODE.
  
 B) MOUNTING CONDITIONS: EG: WALL MOUNTED, BUILT OUT,
 ETC.
  
 C) SHUTTER SPAN.
  
 D) SPECIFIC ANCHOR TO BE USED.
  
 4- CLEARLY MARK ON SHUTTER DRAWINGS SPECIFIC MOUNTING
 CONDITIONS (EG: WALL MOUNTED) AND SPECIFIC ANCHOR TYPE
 AND SPACING TO BE USED ACCORDING TO THE OPENING DESIGN
 PRESSURES,SHUTTER EDGE DISTANCE, CONNECTION TYPE,
 SHUTTER PANEL SPAN AND STRUCTURE TO BE ATTACHED TO
 (CONCRETE, CONCRETE BLOCK OR WOOD).
  