| Plan Review Notes For Permit 08050177 |
| Permit Number |
08050177 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-07 16:58:23 | RESIDENTIAL (R3) SHUTTERS AND WINDOW INSTALLATION, | | | BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- PROVIDE PRODUCT APPROVAL FOR WINDOW AS REQUIRED BY | | | DCA RULE 9B-72. PROVIDE 2 COPIES. | | | | | | 2- PRODUCT APPROVAL SUBMITTED FOR STORM SHUTTERS IS | | | EXPIRED. NOA 03-0417.02 SUBMITTED EXPIRED ON 04/21/08. | | | NEED TO PROVIDE CURRENT PRODUCT APPROVAL AS REQUIRED BY | | | DCA RULE 9B-72. | | | | | | 3- COMPLETE INFORMATION ON INSTALLATION SCHEDULE. | | | PROVIDE THE FOLLOWING INFORMATION: | | | | | | A) SPECIFYOPENING DESIGN PRESSURES. SEE TABLE | | | R301.2(2) OF 2004 FLORIDA RESIDENTIAL CODE. | | | | | | B) MOUNTING CONDITIONS: EG: WALL MOUNTED, BUILT OUT, | | | ETC. | | | | | | C) SHUTTER SPAN. | | | | | | D) SPECIFIC ANCHOR TO BE USED. | | | | | | 4- CLEARLY MARK ON SHUTTER DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS (EG: WALL MOUNTED) AND SPECIFIC ANCHOR TYPE | | | AND SPACING TO BE USED ACCORDING TO THE OPENING DESIGN | | | PRESSURES,SHUTTER EDGE DISTANCE, CONNECTION TYPE, | | | SHUTTER PANEL SPAN AND STRUCTURE TO BE ATTACHED TO | | | (CONCRETE, CONCRETE BLOCK OR WOOD). | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|