| 2008-05-13 09:56:10 | FBC. |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS |
| | AMENDED,THE 2007 FLORIDA STATUTES, AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1}THE 2007 FLORIDA STATUTES |
| | |
| | TITLE XXXII |
| | REGULATION OF PROFESSIONS AND OCCUPATIONS CHAPTER 481 |
| | ARCHITECTURE, INTERIOR DESIGN, AND LANDSCAPE |
| | ARCHITECTURE |
| | 481.229EXCEPTIONS; EXEMPTIONS FROM LICENSURE.-- |
| | |
| | (1)NO PERSON SHALL BE REQUIRED TO QUALIFY AS AN |
| | ARCHITECT IN ORDER TO MAKE PLANS AND SPECIFICATIONS |
| | FOR, OR SUPERVISE THE ERECTION, ENLARGEMENT, OR |
| | ALTERATION OF: |
| | |
| | (A)ANY BUILDING UPON ANY FARM FOR THE USE OF ANY |
| | FARMER, REGARDLESS OF THE COST OF THE BUILDING; |
| | |
| | (B)ANY ONE-FAMILY OR TWO-FAMILY RESIDENCE BUILDING, |
| | TOWNHOUSE, OR DOMESTIC OUTBUILDING APPURTENANT TO ANY |
| | ONE-FAMILY OR TWO-FAMILY RESIDENCE, REGARDLESS OF COST; |
| | OR |
| | |
| | (C)ANY OTHER TYPE OF BUILDING COSTING LESS THAN |
| | $25,000, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER BUILDING |
| | INTENDED FOR PUBLIC USE, PROVIDED THAT THE SERVICES OF |
| | A REGISTERED ARCHITECT SHALL NOT BE REQUIRED FOR MINOR |
| | SCHOOL PROJECTS PURSUANT TO S. 1013.45* THE EXCEPTION |
| | IS NOT MET THEREFORE A DESIGN PROFESSIONAL IS REQUIRED |
| | TO.TAKE RESPONSIBILITY FOR THE PLANS. |
| | |
| | 2} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN |
| | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE |
| | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE |
| | PLAN. |
| | |
| | 3} INDICATE THE TYPE OF FIRE ALARM/DETECTION SYSTEM |
| | WILL BE INSTALLED IN THE UNIT. SEE NFPA-72 CHAPTER 11, |
| | AND CHAPTER 9 FBC. |
| | |
| | 4} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE |
| | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE PUT A ON |
| | THE PLAN FOR CLARITY IN THE FIELD. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |