| Date |
Text |
| 2008-05-07 10:40:10 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | |
| | _XX_1.)TWO COMPLETE COLLATED SETS OF PERMIT |
| | DOCUMENTS REQUIRED.ONE SET OF LOOSE SHEETS PROVIDED. |
| | PLEASE PROVIDE TWO SETS AND STAPLE EACH PRODUCT |
| | APPROVAL. |
| | |
| | _XX_2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY; |
| | MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF |
| | EACH ROOF TYPE |
| | |
| | _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | _XX_4.)PROVIDE A SITE PLAN AND, IF NECESSARY, A |
| | ROOF PLAN SHOWING LOCATION OF AREA OF REROOF.PAPA |
| | SHOWS THIS AS A 316 UNIT (228,505 SF) CONDO; |
| | APPLICATION IS FOR 450SF OF REROOF. |
| | |
| | ____5.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO |
| | BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED |
| | ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB |
| | SHEET). |
| | |
| | _XX_ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| | METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM |
| | ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72. |
| | ENGINEERING MAY BE REQUIRED DEPENDING ON ROOF HEIGHT. |
| | |
| | ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| | |