| 2008-06-20 18:05:02 | |
| | |
| | |
| | DENIED |
| | |
| | THE FOLLOWING COMMENT WERE NOT ADDRESSED IN 1ST REVIEW |
| | |
| | 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $851.56 FOR |
| | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| | |
| | 5)WINDOW TYPE #4 REQUIRES 2X4 MULLION AS STATED ON |
| | SCHEDULE BUT NO PRODUCT APPROVAL WAS SUBMITTED. |
| | *********THE CHANGE THAT IS REQUIRED WAS TO ADD A |
| | PRODUCT APPROVAL FOR 2X4 MULLIONS TO THE SUBMITTAL , |
| | PLEASE SEE THAT THE 1X4 MULLION FOR 100" OPENING WIDTH |
| | AND A 108" OPENING HEIGHT WILL ONLY WORK FOR A DESIGN |
| | PRESSURE OF 22 PSF OR LESS PER PAGE 5 OF THE MULLION |
| | PRODUCT APPROVAL******** |
| | |
| | NEW COMMENTS |
| | |
| | 1)THE PRODUCT APPROVALS FOR THE SINGLE HUNG AND FIXED |
| | WINDOWS WERE NOT RESUBMITTED, PERMIT APPLICATION |
| | PACKAGE MUST BE COMPLETE FOR FINAL STAMPING AND PERMIT |
| | ISSUANCE |
| | |
| | 2)GLASS BLOCK PRODUCT APPROVALS ONLY MEET THE SMALL |
| | MISSILE IMPACT REQUIREMENTS, OPENINGS WITHIN THE FIRST |
| | 30 FEET FROM GRADE MUST MEET LARGE MISSILE IMPACT |
| | CRITERIA PER 1609.1.4 FBC, THE SILICONE SET BLOCK MEETS |
| | THIS REQUIREMENT OR SHUTTERS WILL BE REQUIRED AND THE |
| | PRODUCT APPROVALS SUBMITTED |
| | |
| | 3)ONLY ONE COPY OF LANDSCAPE PLAN AND SOIL REPORT |
| | WERE SUBMITTED |
| | |
| | BLDG PLAN REVIEW |