| Plan Review Notes For Permit 08050084 |
| Permit Number |
08050084 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-20 15:06:42 | ***DENIED*** | | | | | | 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 2) WILL WORK IMPACT FIRE PROTECTION EQUIPMENT? SEPARATE | | | SHOP DRAWINGS AND PERMITS MAY BE REQUIRED FOR EQUIPMENT | | | REMODEL. | | | | | | 3) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED AND | | | SHALL BE MOUNTED AT LOCATIONS TO SATISFY THE 75' TRAVEL | | | DISTANCE REQUIREMENT. | | | | | | 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|