| Plan Review Notes For Permit 08050082 |
| Permit Number |
08050082 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-06 16:02:02 | DOOR AND ROLL UP SHUTTER FOR BUSINESS OCCUPANCY, | | | BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR MOUNTING | | | OF ROLL UP SHUTTERS. SEE ATTACHED SAMPLE OF | | | INSTALLATION SCHEDULE AND COMPLETE ALL THE APPLICABLE | | | INFORMATION. | | | ALSO, MARK ON ROLL UP DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS AND ANCHOR TYPE AND SPACING TO BE USED TO | | | VERIFY COMPLIANCE WITH PRODUCT APPROVAL AND PROPOSED | | | INSTALLATION. | | | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | 2- APPLICATION FOR SHUTTER PROTECTIONWAS ROUTED TO | | | BUILDING OFFICIAL FOR APPROVAL SINCE THIS PROJECT WAS | | | ORIGINALLY APPROVED USING IMPACT DOORS AS REQUIRED BY | | | CITY IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS | | | IMPACT PROTECTION. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|