| Plan Review Notes For Permit 08050063 |
| Permit Number |
08050063 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-12 13:18:39 | RESIDENTIAL ALTERATION, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- PERMIT APPLICATION 07080375 WAS SUBMITTED FOR A | | | CHANGE OF USE FROM SINGLE FAMILY RESIDENCE TO GROUP | | | HOME. THIS APPLICATION EXPIRED BECAUSE NO ACTION WAS | | | TAKEN.NEED TO RE-APPLY FOR A CHANGE OF USE FROM | | | SINGLE FAMILY RESIDENCE TO GROUP HOME AND GET REQUIRED | | | LICENSES TO RUN THE BUSINESS.NEED TO SPECIFY NUMBER | | | OF PERSONS LIVING IN THE FACILITY TO PROPERLY IDENTIFY | | | TYPE OF GROUP HOME AS REQUIRED BY SEC. 310.1 FBC 2004. | | | NEED APPROVAL FROM ZONING. | | | | | | 2- NEED TO CONTACT PALM BEACH COUNTY (2300 N. JOG RD | | | (561)233-5120)TO VERIFY IF IMPACT FEES ARE DUE FOR | | | THE CHANGE OF OCCUPANCY.BRING BACK STAMPED PLANS AND | | | COPY OF PAID RECEIPT IF FEES ARE DUE. | | | | | | 3- STEPS SHOWN ON PROPOSED ADA RAMP DETAIL DON'T COMPLY | | | WITH SEC. R11.5.3.2(RISER TREAD RATIO)ANDSEC. | | | R311.5.3.3 (STAIR NOSING).REVISE AS REQUIRED. | | | | | | 4- ALL DETAILS SHOW SCALE OF DRAWINGS AS1/2" =1'. | | | NOT ALL DETAILS ARE DRAWN TO THIS SCALE. REVISE SCALE | | | ON DRAWINGS AS REQUIRED TO MATCHSCALE OF DRAWINGS. | | | | | | 5- SEPARATE PERMITS ARE REQUIRED FOR ELECTRICAL AND | | | MECHANICALWORK. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|