| Plan Review Notes For Permit 08050050 |
| Permit Number |
08050050 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-05-20 14:28:04 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.IT APPEARS THAT THE ENGINEER HAS USED AN IMPORTANCE | | | FACTOR OF 1 IN DETERMINING COMPONENT AND CLADDING | | | DESIGN PRESSURES.SEE FBC TABLE 1604.5 AND FBC TABLE | | | 1004.1.2.BASED ON SQUARE FOOT AREA, THIS BUILDING | | | APPEARS TO HAVE AN OCCUPANT LOAD OF GREATER THAN 250 | | | (12,500/20SF PER PERSON, OCCUPANT LOAD OF 625 PEOPLE). | | | THIS WOULD REQUIRE AN IMPORTANCE FACTOR OF 1.15. PLEASE | | | CLARIFY OR REVISE PRESSURES/FASTENING. | | | | | | PLEASE NOTE THAT I ATTEMPTED TO REACH THE ENGINEER AND | | | CONTRACTOR TO GET THIS MATTER RESOLVED BY TELEPHONE IN | | | AN ATTEMPT TO EXPEDITE THIS PERMIT, BUT WAS | | | UNSUCCESSFUL. |
|