| 2008-06-26 08:08:33 | RESIDENTIAL (R3) GENERATOR BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISION: |
| | |
| | 1- LETTER SUBMITTED FROM THE MANUFACTURER'S(NORPRO) |
| | ENGINEERING DEPARTMENT STATES THAT UNIT IS NOT DESIGNED |
| | TO WITHSTAND 140MPH WIND LOADS.IF THE UNIT IS NOT |
| | DESIGNED TO WITHSTAND THE WIND LOADS, THEN , WHAT'S THE |
| | PURPOSE OF THE GENERATOR IF IT MAY NOT BE THERE OR IT |
| | MAY NOT WORK AFTER A HURRICANE?.IT ALSO HAS SOME |
| | RECOMMENDATIONS FOR UNIT REINFORCEMENT AND UNIT |
| | ATTACHMENT TO THE CONCRETE SLAB.THEN. IT REQUIRES |
| | INSTALLATION PHOTOS FOR APPROVAL.. THE |
| | MANUFACTURER'S ENGINEERING DEPARTMENT NEEDS TO PROVIDE |
| | COMPLETE INFORMATION SHOWINGTHAT THE UNIT WILL MEET |
| | THE 140 MPH WIND LOAD AND PROVIDE COMPLETE |
| | SPECIFICATIONS SHOWING UNIT ATTACHMENT TO THE CONCRETE |
| | SLAB. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO |
| | VERIFY COMPLIANCE WITH THE WIND LOADS OF SEC. R301 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. ALL INFORMATION NEEDS TO |
| | BE PROPERLY SIGNED AND SEALED AND WITH COMPLETE |
| | ENGINEER'S INFORMATION AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE SUBMITTED WHEN PICKING UP THE |
| | PERMIT. |
| | |