Plan Review Notes
Plan Review Notes For Permit 08050038
Permit Number 08050038
Review Stop B
Sequence Number 2
Notes
Date Text
2008-06-26 08:08:33RESIDENTIAL (R3) GENERATOR BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISION:
  
 1- LETTER SUBMITTED FROM THE MANUFACTURER'S(NORPRO)
 ENGINEERING DEPARTMENT STATES THAT UNIT IS NOT DESIGNED
 TO WITHSTAND 140MPH WIND LOADS.IF THE UNIT IS NOT
 DESIGNED TO WITHSTAND THE WIND LOADS, THEN , WHAT'S THE
 PURPOSE OF THE GENERATOR IF IT MAY NOT BE THERE OR IT
 MAY NOT WORK AFTER A HURRICANE?.IT ALSO HAS SOME
 RECOMMENDATIONS FOR UNIT REINFORCEMENT AND UNIT
 ATTACHMENT TO THE CONCRETE SLAB.THEN. IT REQUIRES
 INSTALLATION PHOTOS FOR APPROVAL.. THE
 MANUFACTURER'S ENGINEERING DEPARTMENT NEEDS TO PROVIDE
 COMPLETE INFORMATION SHOWINGTHAT THE UNIT WILL MEET
 THE 140 MPH WIND LOAD AND PROVIDE COMPLETE
 SPECIFICATIONS SHOWING UNIT ATTACHMENT TO THE CONCRETE
 SLAB. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCE WITH THE WIND LOADS OF SEC. R301 OF
 2004 FLORIDA RESIDENTIAL CODE. ALL INFORMATION NEEDS TO
 BE PROPERLY SIGNED AND SEALED AND WITH COMPLETE
 ENGINEER'S INFORMATION AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE SUBMITTED WHEN PICKING UP THE
 PERMIT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712