2008-05-12 15:33:14GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING
 LENGTHS INDICATED. PLEASE REFERENCE THE RED CIRCLED
 YELLOW HIGH LIGHTED AREAS INDICATING THIS AND COMPLY ON
 THE RESUBMITTAL.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
 *NOTE: NOT ALL PIPING MATERIALS OR PIPE SIZES ARE
 BEING INDICATED FOR ALL CUT SECTIONS OF PIPE. PLEASE
 REFERENCE THE RED CIRCLED YELLOW HIGH LIGHTED AREAS
 INDICATING THIS AND COMPLY ON THE RESUBMITTAL.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE REFERENCE COMMENT #1 AND COMPLY.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 *NOTE: THE SUBMITTED MANUFACTURE SHEETS FOR THE
 GENERATOR, BBQ AND WATER HEATER ARE NOT INDICATING A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY. PLEASE COMPLY ON THE RESUBMITTAL FOR THESE
 ITEMS AND CLEARLY INDICATE THE MAKE AND MODEL NUMBER
 FOR ALL INDICATED MP REGULATORS ON THE RESUBMITTED
 ISOMETRIC. THE ONLY MP REGULATOR BEING INDICATED ON THE
 ISOMETRIC IS AN AMERICAN METER 1813 FOR THE POOL HEATER
 (TYP), HOWEVER THERE IS ALSO A MAXITROL 325 MP
 REGULATOR SUBMITTAL IN THIS PERMIT APPLICATION. PLEASE
 CLARIFY THIS ON THE RESUBMITTAL.
  
 5. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. PLEASE CLEARLY
 INDICATE THE REQUIRED SHUT OFF VALVE FOR THE MP
 REQULATOR BEING INDICATED FOR THE GAS LIGHTS ON THE
 RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  