Plan Review Notes
Plan Review Notes For Permit 08050038
Permit Number 08050038
Review Stop B
Sequence Number 1
Notes
Date Text
2008-06-03 17:00:48RESIDENTIAL (R3) GENERATOR INSTALLATION, BUILDING
 REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-NEED TO PROVIDE INFORMATION SHOWING ATTACHMENT OF
 GENERATOR TO THE SLAB TO RESIST THE 140 MPH WIND LOADS
 INEXPOSURE "C" AS REQUIRED BY SEC. R301.2.1.4 OF 2004
 FLORIDA RESIDENTIAL CODE.INFORMATION SUBMITTED IS A
 DETAIL FOR A CONCRETE SLAB, BUT THERE ARE NO
 DETAIL/SPECIFICATIONS FOR EQUIPMENT ATTACHMENT TO
 RESIST THE ABOVE LOADS.SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 2- NEED TO PROVIDE RECORDED NOTICE OF COMMENCEMENT AS
 REQUIRED BY SEC. 713.13 FLORIDA STATUTES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712