Plan Review Notes
Plan Review Notes For Permit 08050026
Permit Number 08050026
Review Stop B
Sequence Number 2
Notes
Date Text
2008-05-05 14:23:56****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 _XX_4.)FOR THE FLAT ROOF, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 THE ASSEMBLY SELECTED HAS SIX DIFFERENT
 FASTENERS/PATTERNS.PLEASE INDICATE WHICH ONE YOU
 PROPOSE.THIS INFORMATION IS REQUIRED FOR ENHANCED
 FASTENING CALCULATIONS.
  
 _XX_5.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO
 BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED
 ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB
 SHEET).
  
 THE PATTERN SPECIFIED ON THE CONTRACTOR'S LETTERHEAD
 DOES NOT COMPLY FOR ANY OF THE SIX DIFFERENT FASTENERS
 (ZONES 2 AND 3).
  
  