| 2008-05-05 08:58:26 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3 |
| | (4)(6)(13) PLUMBING: PLEASE SUBMIT A PLUMBING SANITARY |
| | ISOMETRIC RISER DIAGRAM OF THE PROPOSED SINK IN THE |
| | W.I.C. INDICATING THE WASTE, VENT, TRAP WITH SIZE AND |
| | IF APPLICABLE CLEANOUT LOCATION. |
| | |
| | 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3 |
| | (3)(8)(10)(13) PLUMBING: AN ISOMETRIC POTABLE WATER |
| | RISER DIAGRAM IS REQUIRED FOR THE PROPOSED SINK IN THE |
| | W.I.C. WORK FOR BOTH THE HOT AND COLD WATER INDICATING |
| | THE PIPE SIZES, VALVE LOCATIONS, LOCATION OF THE WATER |
| | SUPPLY LINE WITH BACKFLOW PREVENTER**608 (IF THERE IS |
| | AN EXISTING BACKFLOW PREVENTER, PLEASE CLEARLY INDICATE |
| | THIS). |
| | |
| | 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| | NOTE: ONE SUBMITTED SHEET HAS AN ARCHITECTURAL TITLE |
| | BLOCK THAT NEED TO BE SIGNED,SEALED,DATED WITH LICENSE |
| | NUMBERS (FIRM LICENSE. |
| | |
| | 4. VALUE FOR THE PROPOSED WORK APPEARS LOW. |
| | PER FBC-2004, CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | END OF COMMENTS: |
| | |