2008-05-15 15:44:30*****DENIED*****
  
  
 1. THE ADDRESS OF THE PROJECT SITE , INCLUDING SUITE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 2.THE SUBMITTED PLANS SHALL BE DRAWN DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH,
 OR OTHER ACCEPTABLE MEDIUM.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH ACCESS TO OR EGRESS FROM THE FIFTH FLOOR AND/OR
 THE BUILDING.
  
 5.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 6.SPECIFY THE NEW WALL INTERIOR FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 7.WILL THE SCOPE OF WORK HAVE CAUSE FOR LIFE SAFETY
 DEVICES SUCH SMOKE ALARMS AND/OR FIRE SPRINKLERS TO BE
 RELOCATED?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722