| Date |
Text |
| 2008-05-05 12:43:59 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC CHAPTER 1AS AMENDED AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} INDICATE THE LOCATION OF ALL ADDED ELECTRICAL | | | DEVICES ND LIGHTING ON A SEPARATE ELECTRICAL SHEET. | | | | | | 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.1.3.FBC. | | | | | | 4} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE | | | PLANS PER 106.1.1 FBC AS AMENDED. | | | | | | 5} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE | | | SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|