Plan Review Notes
Plan Review Notes For Permit 08050006
Permit Number 08050006
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-22 11:54:42** DENIEDREVIEW**
  
  
 1) NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR NEW CATH-LAB
 PANEL.
 408.4, 240.4, 310.16 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 2) NOTE: PLEASE SHOW LOCATION OF NEW CATH LAB PANEL
 COMPARED TO ATS-11. TAPPED CONDUCTOR RULES PER 240.21
 CAN NOT BE VERIFIED AT THIS TIME.
  
 3) NOTE: PLEASE SUBMIT THE LIGHTING PERFORMANCE
 CALCULATION PER 13-415.2, 13-415.2.ABC.1.1, .1.2.
 THE SUBMITTED PHOTO-COPIED FORM IS NOT COMPLETED, NOT
 ORIGINAL, NOT SIGNED AND SEALED ETC.
 FBC 13-103.1
  
 4) NOTE: PLEASE VERIFY COMMENT #2 ABOVE AND VERIFY
 500MCM IN 150AMP BREAKER.
 110.3, 90.7
  
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  