| 2008-05-29 16:28:25 | NEW STREET LIGHT POLES, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENTDESCRIBING | | | THIS SCOPE OF WORK AS REQUIRED BY SEC. 713.13 FLORIDA | | | STATUTE. | | | | | | 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. | | | NEED TO UPDATE VALUE TO INCLUDEREMOVAL OF EXISTING | | | POLES, ENGINEERING,SPECIFIC LIGHT POLE AND LIGHT | | | FIXTURE TO BE USED AND CONTRACTOR'S OVERHEAD AND | | | PROFIT. SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 3- PROVIDE COMPLETE ENGINEERING CALCULATIONS TO SHOW | | | COMPLIANCE WITH SEC.1604,1609.1.1AND 1609.1.3 FBC | | | 2004. | | | NOTE: ALSO, SEE NOTE #4OF LIGHT POLE DETAIL ON SHEET | | | E-2 SUBMITTED ( NOTE: INFORMATION ON LIGHT POLE DETAIL | | | NOTE #4 AND DESIGN INFORMATION ON FOUNDATION NOTES ON | | | SHEET E-2 DOESN'T MATCH. REVISE AS REQUIRED). | | | | | | 4- PROVIDE SPECIFICATIONS/CUT SHEETS FOR LIGHT POLE AND | | | LIGHT FIXTURE TO SHOW COMPLIANCE WITH THE CALCULATED | | | DESIGN CRITERIA. SEC. 106.1.2 CITY A MENDMENTS TO FBC | | | 2004 TO VERIFY COMPLIANCE WITH PROPOSED STRUCTURE AND | | | THE CALCULATED WIND LOADS OF SEC. 1609 FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|