| 2008-05-05 17:12:35 | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,NFPA |
| | 303 2000,2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 |
| | FBC CHAPTER 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE |
| | FOLLOWING: |
| | |
| | 1} THE STANDARD REFERENES ON SHEET G-2, APPLICABLE |
| | CODES SECTION, SHOULD BE CHANGED TO THE ABOVE EDITIONS |
| | AS THAY ARE CURRENTLY IN EFFECT. |
| | |
| | 2} NFPA 303 ARTICLE 3.3.1 |
| | A BENCH MARK INDICATING THE ELECTRICAL DATUM PLANE OF |
| | THE LAND AREA SHALL BE PERMANENTLY LOCATED ON SHORE IN |
| | THE MARINA OR BOATYARD.INDICATE THE LOCATION OF SAME. |
| | |
| | 3} 555.2(3) (3) THE ELECTRICAL DATUM PLANE FOR FLOATING |
| | PIERS AND LANDING STAGES THAT ARE (A) INSTALLED TO |
| | PERMIT RISE AND FALL RESPONSE TO WATER LEVEL, WITHOUT |
| | LATERAL MOVEMENT, AND (B) THAT ARE SO EQUIPPED THAT |
| | THEY CAN RISE TO THE DATUM PLANE ESTABLISHED FOR (1) OR |
| | (2), IS A HORIZONTAL PLANE 762 MM (30 IN.) ABOVE THE |
| | WATER LEVEL AT THE FLOATING PIER OR LANDING STAGE AND A |
| | MINIMUM OF 305 MM (12 IN.) ABOVE THE LEVEL OF THE |
| | DECK. |
| | 555.9 ELECTRICAL CONNECTIONS |
| | ALL ELECTRICAL CONNECTIONS SHALL BE LOCATED AT LEAST |
| | 305 MM (12 IN.) ABOVE THE DECK OF A FLOATING PIER. ALL |
| | ELECTRICAL CONNECTIONS SHALL BE LOCATED AT LEAST 305 MM |
| | (12 IN.) ABOVE THE DECK OF A FIXED PIER BUT NOT BELOW |
| | THE ELECTRICAL DATUM PLANE.INDICATE COMPLIANCE WITH |
| | THESE ARTICLES FOR THE JUNCTION BOX AND LUMINAIRE |
| | CONNECTIONS.SHEET EP1.02 HAS NO DIMENSIONS FROM THE |
| | WATERLINE. |
| | |
| | 4} INDICATE THE CABLE DESIGNATION FOR THE "FLEX CABLE" |
| | SHOWN ON SHEET EP1.02. SEE ARTICLE 555.13(A)(2)FOR TYPE |
| | ALLOWED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |