Plan Review Notes
Plan Review Notes For Permit 08040824
Permit Number 08040824
Review Stop M
Sequence Number 6
Notes
Date Text
2008-11-04 08:38:42PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS
 *** DENIED ***
  
 1) THE COOLING LOAD CALCULATIONS NEED TO BE REVISED AS
 THE A/C EQUIPMENT AND THE ENGINEER OF RECORD HAS
 CHANGED, PER 13-407.1.ABC.1.1.
  
 2) OUTSIDE AIR CALCULATIONS ARE INCORRECT, SEE ATTACHED
 COPY OF THE ARCHITECTURAL PLAN'S SQUARE FOOTAGE AND
 SEATING CAPACITY. PLEASE CORRECT PER 2004 FBC/M 403.3.
 (ALSO THE OUTSIDE AIR CALCULATIONS ARE MISSING THE BAR
 AREA).
  
 3) OUTSIDE AIR CALCULATIONS SHOW 'ADJUST PER EXCEPTION
 403.3. THE EXCEPTION READS "EXCEPTION: THE OCCUPANT
 LOAD IS NOT REQUIRED TO BE DETERMINED, BASED ON THE
 ESTIMATED MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE
 403.3 WHERE APPROVED STATISTICAL DATA DOCUMENT THE
 ACCURACY OF AN ALTERNATE ANTICIPATED OCCUPANT DENSITY".
 PLEASE SUBMIT A COPY OF THE CODE SECTION THAT PERMITS A
 50% REDUCTION OF OUTSIDE AIR.
  
 4) THE AIR BALANCE DIAGRAM IS INCORRECT. SEE ATTACHED
 COPY OF HOOD PLAN FOR THE KITCHEN HOOD FANS. PLEASE
 CORRECT PER 2004 FBC 13-409.1.ABC.3.6.1.
  
 5) THE PLAN SHOWS FLEXIBLE DUCT BEING USED AT THE
 BATHROOM EXHAUST FANS. EXHAUST DUCTS SHALL BE METAL,
 PER 2004 FBC 501.4.
  
 6) THE 200,000 BTU GAS WATER HEATER IN THE JANITOR'S
 CLOSET IS A CONFINED SPACE, SEE 2004 FBC/FG 304.5.1.
 PLEASE PROVIDE FOR COMBUSTION AIR PER 2004 FBC/FG 304.1
 IF THE TRANSFER GRILL IS FOR COMBUSTION AIR, SEE 2004
 FBC/FG 304.6.2 ONE PERMANENT OPENING. PLEASE CORRECT.
  
 7) THE JANITOR'S CLOSET ALSO HAS AN EXHAUST FAN IN IT,
 PLEASE PROVIDE FOR MAKE-UP AIR TO THE GAS WATER HEATER,
 PER 2004 FBC/FG 304.4 AND 304.9.1.
  
 8) PLEASE PROVIDE COMBUSTION AND MAKE-UP AIR
 CALCULATIONS FOR THE GAS WATER HEATER, PER 2004 FBC/FG
 304.
  
 9) PLEASE SHOW THE SIZE OF THE EXISTING OUTSIDE AIR
 DUCTWORK AS ONE IS SUPPLING TWO 14" OUTSIDE AIR DUCTS,
 SEE 2004 FBC/M 603.2.
  
 10) A/C SYSTEM MODEL NUMBERS AHU 40RM-012H AND ACU
 38ARD014 LISTED ON THE A/C EQUIPMENT SCHEDULE COULD NOT
 BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE SUBMIT
 MANUFACTURE SPECIFICATION SHEETS, PER 2004 FBC
 13-407.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]