| 2008-11-13 10:22:25 | REVISION DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | 1. SHTS P-1 & P-2 DRAWING REFERENCE NOTES 5A, (P-1), |
| | AND GAS RISER DIAGRAM, (P-2), INDICATE THE MANUAL SHUT |
| | OFF VALVE AND EMERGENCY SHUT OFF VALVE UP IN THE |
| | CEILING. THIS IS NOT APPROVED. ALSO THERE IS NO |
| | REQUIRED UNION INDICATED DOWNSTREAM OF THE MANUAL SHUT |
| | OFF VALVE. (SEE THE FOLLOWING): |
| | __ EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | 2. SHTS P-1 & P-2 THE FLOOR PLAN, GAS SYSTEM |
| | CALCULATIONS TABLE & THE GAS RISER DIAGRAM SHOW ITEM |
| | 18, PIZZA OVEN. PER THE CONTRACTOR, ITEM 18 HAS BEEN |
| | DELETED. THIS WAS INDICATED WHEN THE CONTRACTOR APPLIED |
| | FOR THE GAS PERMIT. THE PROVISO INDICATED ON THE PLANS |
| | REQUIRED MANUF. SPECIFICATION SHEETS FOR ITEM 18. THE |
| | GAS PERMIT WAS ISSUED WITH THE STIPULATION THAT THE |
| | REVISIONS DELETES ITEM 18. |
| | |
| | 3. SHT P-2 GAS SYSTEM CALCULATIONS BTU'S DO NOT REFLECT |
| | THE MANUF. SPECIFICATION SHEETS SUBMITTED PLEASE |
| | CORRELATE. THE FURTHEST OUTLET IS 145 FEET NOT 140 FEET |
| | AS INDICATED. THIS IS WITH THE LENGTH OF PIPE FROM THE |
| | METER TO THE FIRST RISE, (11 FEET OF 2-1/2" PIPE), THE |
| | LENGTH OF PIPE THRU THE OUTSIDE WALL THRU SLEEVE, AND |
| | THE LENGTH OF DROP DOWNSTREAM OF THE SLEEVED PIPE. |
| | PLEASE INDICATE ALL PIPE LENGTHS AND RECALCULATE TOTAL |
| | DEVELOPED LENGHT AND INDICTE ON THE GAS SYSTEM |
| | CALCULATIONS. |
| | |
| | 4. SHT P-2 GAS RISER DIAGRAM HAS SOME PIPE SIZING THAT |
| | IS INCORRECT. 1-1/4" PIPE IS REQUIRED TO THE SHUT OFF |
| | VALVE TO THE WATER HEATER. (1" INDICATED). -- 2" PIPE |
| | IS REQUIRED UP TO ITEM NUMBER 13, (NO PIPE SIZE |
| | INDICATED). -- 1-1/2" REQUIRED UP TO ITEM 10, (NO PIPE |
| | SIZE INDICATED). -- 1-1/4" REQUIRED UP TO ITEM 11, (NO |
| | PIPE SIZE INDICATED). -- 1" REQUIRED UP TO ITEM 9, (NO |
| | PIPE SIZE INDICATED). -- THE FOLLOWING STUB OUTS TO THE |
| | APPLIANCES ARE NOT CORRECT. -- 1" REQUIRED TO SHUT OFF |
| | VALVE FOR ITEM 15. -- 1-1/4" REQUIRED UP TO THE SHUT |
| | OFF VALVES FOR ITEMS 17, 13 & 10. |
| | |
| | 5. SHT P-3 FOOD SERVICE PLUMBING EQUIPMENT SCHEDULE. |
| | REVISIED MANUFACTURE & MODEL NUMBER CHANGED TO READ |
| | "REFER TO KITCHEN CONSULTANT DRAWINGS". KITCHEN |
| | CONSULTANT DRAWINGS WERE NOT SUBMITTED. IF THE GAS |
| | EQUIPMENT HAS CHANGED, THEN THE MANUFACTURE |
| | SPECIFICATION SHEETS FOR THE GAS EQUIPMENT SHALL BE |
| | SUBMITTED AND SHALL CORRELATE WITH THE GAS LOAD |
| | INDICATED ON THE GAS RISER DIAGRAM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |