2008-09-02 16:17:52** DENIED/TEMPORARY FAILED **
  
 1) NOTE: LIGHTING PERFORMACE CALCULATIONS LOCATED IN
 THE PLUMBING SUBMITTALS FOR KITCHEN EQUIPMENT.
 CALCULATIONS WERE REVIEWED. MINOR CORRECTION NEEDED.
 SPOKE TO ENGINEER AND WILL SEND NEW SHEETS ALONG WITH
 SHEETS E-1, E-4 AND E-5 BEING REVISED.
 ALSO PER MECHANICAL COMMENTS NEED NEW SHEET M-4. SPOKE
 TO DAVIS PUGA AS SHEETS IN BOTH SETS ARE NOT SIGNED,
 DATED OR SEALED. THEY CONTAIN A DIGITAL SEAL AND COLOR
 DIGITAL SIGNATURE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717